Benchmark Platinum-Edge [II]: Operation-Service Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY
OPTION 3 Instructions: Outdoor Reset, Direct Wired Header Temp Sensor & Outdoor Temp
Sensor
Step 3 – OPTION 3 CONFIGURATION
On All Boiler:
1. Go to:
Main Menu
Set the Unit Mode parameter to BST Client.
2. Go to:
Main Menu
Set the Unit Address parameter to the communication address of the unit.
On the BST Manager only:
Main Menu → Advanced Setup → BST
1. Go to
in each menu in the table below.
Menu/Screen Name
Cascade
Configuration
Application
Configuration
Cascade
Communication
OMM-0137_E • GF-211 •
12/13/2019
Advanced Setup
Advanced Setup
Parameters
Unit Mode
Hdr Temp Sensor
Application
SH Operating Mode
Outdoor Temp Sensor
Plant Setpoint
Min Address
Max Address
Cascade Baud Rate
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
BST Cascade
Cascade
BST Cascade
Cascade
Cascade, set the Parameters to the Values
Values
BST Manager
Header Temp
Space Heating
Outdoor Reset
Outdoor Sensor
Header temperature required for the cascade
The minimum unit address in the cascade
The maximum unit address in the cascade
The baud rate for the cascade.
Configuration:
Communication:
Page 94 of 153