1MAC456939-IB D
620 series ANSI
Operation Manual
A071168-ANSI V2 EN
Figure 87:
Selecting the setting group value
Only values within the selected setting group can be changed.
7.
Press
or
to change the value and
A070922-ANSI V2 EN
Figure 88:
Editing the setting group value
The active setting group is indicated with an asterisk * .
Activating a setting group
Protection relay settings are planned in advance for different operation conditions by
calculating setting values to different setting groups. The active setting group can be
changed by the protection relay application or manually from the menu.
1.
Select Main menu/Settings/Setting group/Active group and press
Commissioning
to confirm the selection.