Ebyte E180-DTU User Manual page 37

Hide thumbs Also See for E180-DTU:
Table of Contents

Advertisement

Chengdu Ebyte Electronic Technology Co.,Ltd.
As an optimization of multi-host request performance, the storage gateway can only work in TCP server mode, which improves the
response speed of the network side.
Peculiarity:
(1) The gateway has a 5K cache for storing instructions and returning results (reading 10 hold registers for example, can store 189
instructions and returned results);
(2) The RTU response timeout automatically clears the cache to ensure the real-time and authenticity of the data;
(3) The polling interval can be customized, 0-65535ms;
(4) The gateway polls the RTU device according to the storage time of the configured instruction, and the MODBUS host does not
query the instruction again during the storage time, and the gateway automatically deletes the storage instruction to release the
cache;
(5) The first command and control command (05, 06, 0F, 10 function code) will directly access the RTU device;
(6) Only 01, 02, 03, and 04Modbus function code query result storage is supported;
Storage gateway host computer and web page configuration:
Copyright ©2023,成都亿佰特电子科技有限公司
E18-DTU(Z27-ETH) User Manual