Connecting
6.3 Connecting terminal blocks
Procedure for spring-loaded terminal blocks
~10°
~10°
1. To release the clamping springs, insert the 3 mm flat-head screwdriver as far as it will
go into the square opening of the spring-loaded terminal. Please observe a 10° horizontal
angular deviation of the screwdriver to the oval opening.
2. Insert the cable into the oval opening as far as it will go.
3. Hold the cable in the spring-loaded terminal.
4. Pull out the screwdriver.
5. Pull on the cable to ensure it is clamped tight.
44
3 mm
Equipment Manual, 08/2023, A5E50307927002A/RS-AA/001
3TK2810-0 standstill monitor