YASKAWA CIMR-DC2A0050BAA Quick Start Manual page 70

Power regenerative converter
Table of Contents

Advertisement

11 UL Standards
Model
Terminal
R/L1, S/L2, T/L3
,
4A0030
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
,
4A0040
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
,
4A0060
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
,
4A0100
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
,
4A0130
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
,
4A0185
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
,
4A0270
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
,
4A0370
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
,
4A0630
r1/ 11, 1/ 21, t1/ 31
70
Recommended
Gauge
AWG, kcmil
6
14
6
4
14
6
2
14
6
3 × 2P
1/0 × 2P
14
3
3/0 × 2P
14
1/0
3/0 × 2P
14
1/0
300 × 2P
14
2/0
4/0 × 4P
14
4/0
4/0 × 8P
14
250
YASKAWA ELECTRIC TOEP C710656 06E YASKAWA Power Regenerative Converter - D1000 Quick Start Guide
Wire Range
Screw Size
AWG, kcmil
6 to 2/0
M8
14 to 10
M4
8 to 6
M8
4 to 2/0
M8
14 to 10
M4
6
M8
2 to 2/0
M8
14 to 10
M4
6
M10
3 to 2/0
M8
1/0 to 2/0
14 to 10
M4
3
M10
3/0 to 600
M10
14 to 10
M4
1/0 to 2/0
M10
3/0 to 600
M12
14 to 10
M4
1/0 to 4/0
M12
300
M12
14 to 10
M4
2/0 to 4/0
M12
4/0 to 300
M12
14 to 10
M4
2/0 to 300
M12
4/0 to 300
M12
14 to 10
M4
2/0 to 300
M12
Tightening Torque
Nm (lbin.)
5.4 to 6.0 (47.8 to 53.1)
1.1 to 1.2 (9.7 to 10.6)
9.0 to 11 (79.7 to 97.4)
5.4 to 6.0 (47.8 to 53.1)
1.1 to 1.2 (9.7 to 10.6)
9.0 to 11 (79.7 to 97.4)
5.4 to 6.0 (47.8 to 53.1)
1.1 to 1.2 (9.7 to 10.6)
18 to 23 (159 to 204)
5.4 to 6.0 (47.8 to 53.1)
1.1 to 1.2 (9.7 to 10.6)
18 to 23 (159 to 204)
18 to 23 (159 to 204)
1.1 to 1.2 (9.7 to 10.6)
18 to 23 (159 to 204)
32 to 40 (283 to 354)
1.1 to 1.2 (9.7 to 10.6)
32 to 40 (283 to 354)
32 to 40 (283 to 354)
1.1 to 1.2 (9.7 to 10.6)
32 to 40 (283 to 354)
32 to 40 (283 to 354)
1.1 to 1.2 (9.7 to 10.6)
32 to 40 (283 to 354)
32 to 40 (283 to 354)
1.1 to 1.2 (9.7 to 10.6)
32 to 40 (283 to 354)