Make sure the protective earthing conductor complies with technical standards and local safety regulations.
Because the leakage current exceeds 3.5 mA in model 4A0630, IEC/EN 61800-5-1:2007 states that either the power
supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective
earthing conductor with a cross-section of at least 10 mm
result in death or serious injury.
Use appropriate equipment for residual current monitoring/detection (RCM/RCD).
This converter can cause a residual current with a DC component in the protective earthing conductor. Where a
residual current operated protective or monitoring device is used for protection in case of direct or indirect contact,
always use an RCM or RCD of type B according to IEC/EN 60755.
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the converter matches the voltage of the incoming power supply before applying power.
When installing an IP00/IP20 converter in a closed panel or cabinet, sufficiently cool the panel or cabinet with a
cooling fan or air conditioner so that the air temperature entering the converter is 50°C or cooler.
Failure to comply could result in overheating and fire.
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Do not install the converter to a combustible surface. Never place combustible materials on the converter.
Only allow qualified personnel to operate a crane or hoist to transport the converter.
Failure to comply may result in serious injury or death from falling equipment.
Do not carry the converter by the front cover or the terminal cover.
Failure to comply may result in minor or moderate injury from the main body of the converter falling.
Hold the specified locations when carrying a harmonic filter module by hand.
Holding any other location when carrying the harmonic filter module could cause the module could fall and cause
injury.
Carry all standard configuration and peripheral devices in a method suitable for the weight of the device.
Incorrectly handling devices could cause them to fall and result in injury or damage to the device.
6
W ARNING
2
Fire Hazard
Crush Hazard
CAUTION
YASKAWA ELECTRIC TOEP C710656 06E YASKAWA Power Regenerative Converter - D1000 Quick Start Guide
(Cu) or 16 mm
2
(Al) must be used. Failure to comply may