Dil Switch Selector; Host Settings - Bosch APC-AMC2-4R4CF Installation Manual

Access modular controller 2
Hide thumbs Also See for APC-AMC2-4R4CF:
Table of Contents

Advertisement

Access Modular Controller 2
4.11

DIL switch selector

4.11.1

Host settings

DIL switches are used to configure the host settings. The first four DIL switches for address
selection define the RS-485 address of the AMC2 in a RS-485 bus system. Switch 5 selects
one of the two different protocols, SDEB and BPA (according to DIN6619).
Switch 6 sets the connection to the host system to either RS-232 or RS-485.
Notice!
If using an Ethernet connection, set switch 1 to ON (= factory setting).
If using an RS-232 connection, set the address by configuring it in the Access Control System.
This is a point-to-point connection that is usually configured as address 1, so set switch 1 to
ON.
Figure 4.13: Location of the selector for host settings
Address
None
1
2
3
4
5
6
7
8
Tab. 4.1: Setting the address via the DIL switch
Instructions for DIL switch 5
Set SDEB (= DIL switch 5 to ON) in the following cases
Set BPA (= DIL switch 5 to OFF) in the case of an
Bosch Security Systems B.V.
DIL Switches
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
Ethernet host connection
RS-485 host connection, provided only one AMC2 is connected on the bus
3
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
Installation manual
Installing | en
25
2020-01 | V02 |