Wiegand Interface for Card Readers 4.13.1 Connecting different reader types 4.14 RS-485 Interface for Card Readers 4.15 RS-232 Interface for Card Readers 4.16 Connecting Relay Outputs 4.17 Connecting Analog Input Devices 4.18 Tamper Protection Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 4
Access Modular Controller 2 Operating Status Display of the AMC2 Configuring the Ethernet Interface Troubleshooting 5.3.1 Resetting the Software 5.3.2 Resetting the Device to Factory Default Technical Data Appendices Connecting Diagrams Index 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
10. Lightning - For added protection during electrical storms external lightning conductors can be installed. This prevents power surges from damaging the unit. 11. The units should be installed in locations with restricted access. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
0°C to 50°C. Disposal Your Bosch product is designed and manufactured with high-quality materials and components which can be recycled and reused. This symbol means that electrical and electronic equipment, at their end-of-life, should be disposed of separately from your household waste.
Do not attempt to put the unit into operation if components are damaged. If any parts are missing, inform your customer service representative or a Bosch Security Systems salesperson. The shipping carton is the safest transport container for the unit. Store it and the other packaging material for future use.
Bosch Security Systems retains all rights not expressly granted. Nothing in this license constitutes a waiver of Bosch’s rights under the U.S. Copyright laws or any other federal or state law. If you have any questions concerning this license, please, write to:...
Introduction Description The APC-AMC2-4R4CF (also called AMC2-4R4, AMC2, or controller) is equipped with four independent interfaces for RS-485 type readers. It is able to control up to four doors with a reader in each direction and up to eight doors with a reader in one direction only.
Page 10
| Introduction Access Modular Controller 2 Figure 3.3: The Access Modular Controller AMC2-4W Figure 3.4: The Access Modular Controller AMC2-4R4 Figure 3.5: The extension module AMC2-4WE Figure 3.6: The IO-Controller AMC2-16ION 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 11
The AMC2-4W can be extended by a maximum of one AMC2-4WE plus a maximum of three I/O extension modules. The I/O extension modules AMC2-8IOEAMC2-16IOE (in any combination) are, like the AMC2-4WE, connected via the AMC2-4W’s extension interface. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 12
An AMC2-4W can have an additional interface extension module AMC2-4WE, so that the number of inputs and outputs grow up to 64. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 13
Figure 3.10: Example of an entrance configuration with an AMC2-2R2 The AMC2-4R4 communicates with the host system primarily by ethernet. In special configurations the RS-485 interface can also be used for the host connection. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
3.1.1 Extension AMC2-16IOE The extension board AMC2-16IOE can be used with an AMC2 controller. It serves additional inputs and outputs. Figure 3.11: The extension board AMC2-16IOE 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
The AMC2-8IOE is identical in all respects to the AMC2-16IOE except in the number of inputs and outputs. Information in this manual refers to all three extensions described here, unless explicitly stated otherwise. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
The AMC2-16IE is identical in all respects to the AMC2-16IOE except in missing outputs. Information in this manual refers to all three extensions described here, unless explicitly stated otherwise. Equipment Configuration Figure 3.14: Upper circuit board with display (top side) 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 17
NOTICE: In order to avoid an error message caused by an earlier voltage drop we suggest to replace the battery every 8 years. Spare part: VARTA CR 2032 PCB. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 18
AMC2-4R4 internal power supply (“wet” mode). Push button, available on top of the housing to select different display modes. Jumper: Potential equalization between different systems and earth ground (shield) for the bus systems. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 19
Access Modular Controller 2 Introduction | en Reset push button - reachable through the casing using a screwdriver Figure 3.18: Overview - Interfaces Figure 3.19: Overview - Interfaces Figure 3.20: Overview - Interfaces Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 20
Figure 3.22: Overview - Interfaces Figure 3.23: Overview - Interfaces RS-485 extension module bus External tamper contact Connector for power supply RS-485 interfaces for up to 8 card readers Connectors for eight analog inputs 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 21
Connectors for 16 relay outputs Configurable RS-485 host interface or extension interface External tamper contact RS-232 reader interface Wiegand reader interfaces Connectors for six analog inputs Connectors for six relay outputs RS-485 reader bus Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 22
All connectors, with the exception of the RS-232 and Ethernet host interface, are pluggable screw clamp terminals. Figure 3.24: Jumper at the bottom side Figure 3.25: Jumper at the bottom side Figure 3.26: Parts at the bottom side 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 23
Jumper: Equalization of potential between different systems and earth ground (shield) for the extension interface. Jumper for setting either voltage free relay output (“dry” mode) or looped-in voltage from the AMC2 internal power supply (“wet” mode). Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 24
Jumper for setting either voltage free relay output (“dry” mode) or looped-in voltage from the AMC2 internal power supply (“wet” mode). Jumper: Equalization of potential between different systems and earth ground (shield) for the extension interface. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 25
8 years. Spare part: VARTA CR 2032 PCB. Notice! For details on the setting of the jumpers and DIL switches listed here, please see DIL switch selector, page 61. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
10V - 30Vdc - max. 3 A – or over the RS-485 host connector – Information about the inputs and outputs on the display of the AMC2 controller – Tamper contact for external covers 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
(UPS). Notice! If an external power supply is used, this should also guarantee an uninterruptable power supply (UPS). Example: Bosch power supply APS-PSU-60 (F.01U.282.970). System Overview The Access Controller AMC2-4R4 is connected between the management host system and different peripheral devices.
Page 28
Host AMC2-4R4 Card reader (1 - 8) Communication and power supply Ethernet System configurations for Access Control applications – The minimum configuration consists of: – one PC with system software, 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 29
AMC enclosures. Figure 3.33: System overview Host Ethernet AMC2-4R4 RS-232 connection (for special control functions) RS-485 connection for max. two readers Wiegand connection Figure 3.34: System overview Host AMC2-4W Card reader Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 30
| Introduction Access Modular Controller 2 Communication and power supply AMC2-4WE Figure 3.35: System overview Host AMC2-Controller Card reader Communication and Power supply AMC2-Extension Ethernet Figure 3.36: System overview Host Ethernet Access Controller 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 31
Using Wiegand reader interfaces, up to four peripheral devices can be connected to each AMC2-4R4. The interfaces are point-to-point connections, meaning that only one reader can be connected to one interface. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 32
The extension interface supports up to three additional I/O boards (AMC2-8IOE, AMC2-16IE, or AMC2-16IOE). All extension boards are controlled by the AMC2 and are freely combinable. Notice! This controller is currently a project version. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
[2]. Figure 4.1: Mounting the AMC2 on a mounting rail Figure 4.2: Mounting the AMC2 device on a mounting rail Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Push down the AMC2-4W until the lower edge snaps out of the mounting rail [1]. Pull the lower end of the AMC2-4W from the mounting rail [2]. Figure 4.3: Unmounting the AMC2 from a mounting rail 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 35
Access Modular Controller 2 Installing | en Figure 4.4: Unmounting the AMC2 device from a mounting rail Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
The AMC2-4W case consists of a top cover mounted with a two-point snap-in closure on a chassis. To open the case, push down the two snap-ins with a screwdriver, then swing the cover down. Figure 4.5: Opening the AMC2 case Figure 4.6: Opening the AMC2-2R2 case 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 37
Access Modular Controller 2 Installing | en Figure 4.7: Opening the AMC2-DCUA case Figure 4.8: Opening the AMC2-4WE case Figure 4.9: Opening the AMC2-16ION case Figure 4.10: Opening the AMC2-16IOE case Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 38
| Installing Access Modular Controller 2 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
[1]. Please ensure that the BOSCH logo is not upside-down. The upper edge of the front cover now aligns with the two-point snap-in closures on the upper edge of the back cover [2], and may thus be clicked gently into place.
With the calculation below you can find out which cable type must be used. If you connect the power supply and the AMC-device with the delivered cable set from the enclosure the calculation is not necessary. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 41
These specifications apply to power supply, readers, relay outputs, and extension interface. Regarding inputs, specific voltage-drop values need to be taken into account. Refer to Connecting Analog Input Devices, page 82. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
If the devices have their own power supplies, the shielding is applied to one side only. The free end should be insulated to avoid inadvertent connections. If one device is fed power by another, the cable shielding should be applied to both sides. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
If the ground conductor and the shield on the host are not connected and: – no party line exists, the jumper JP1 is set (= A2) – a party line exists, the jumper JP1 is set at the first device only (= A2) Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Grounding for Extension Interface B 1: Delivery status B 2: Figure 4.16: Location of ground jumper bottom side Figure 4.17: Location of ground jumper bottom side Figure 4.18: Location of ground jumper bottom side 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
AMC2 to the RS-485 ground of the bus. Only set jumper C and D (C2 or D2) if the AMC2 powers all other peripheral devices which are directly connected to the AMC2. Bosch Access Systems V.B. Installation manual...
UPS is connected to the following pins: – pin 4 and 7 for power good AC – pin 5 and 7 for power good Battery – pin 6 and 7 for power good DC 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Figure 4.25: Location of the power supply connector Connect an external power supply (10 - 30 Vdc) for AMC2-4R4 at pin 1 (positive) and pin 3 (0 V) of the pluggable screw connector. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
The power can also be supplied by the AMC2-4W. In this case power pins 1 and 2 should be connected, as well as data lines on pins 3 - 6. Figure 4.26: Interface for internal power supply Figure 4.27: Interface for internal power supply 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 50
Tab. 4.1: Overview - power supply and power consumption Figure 4.29: Example configurations Example Used components Output available Constant power Usage load PS + AMC2 60VA 55VA 25VA PS + AMC2 + 60VA 2 x 5VA 50VA 20VA 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 51
25VA PS + AMC2-4WE 36VA 31VA 25VA PS + AMC2-4W 36VA 31VA 25VA PS + AMC2-4WE + 36VA 2 x 5VA 26VA 20VA Extension using further Extensions the values decrease Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 52
AMC2 itself . This leaves 31VA to support external devices. 25VA of these 31VA can be used for constant load (e.g. a card reader) leaving 6VA for occasional peak usage (e.g. a door opener). 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Use a CAT5 or higher version to connect the AMC2-4W with the network. A complete connection diagram of the Ethernet host interface is shown in chapter Connecting Diagrams, page 102. Figure 4.30: Location of the Ethernet interface Figure 4.31: Location of the Ethernet interface Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 54
You can accelerate this process by running the following command: ipconfig /flushdns This makes the AMC2 device immediately available by its name. Notice! Using the Ethernet connection, the switches 1 and 5 must remain in Pos. ON (=factory setting). 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
An RS-485 host system can consist of up to eight AMC2 controllers connected using 2- or 4- wire connection. Figure 4.33: Configuration of a RS-485 host system Host RS-232 connection RS-232 / RS-485 converter RS-485 bus AMC2 controller Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 56
RS-485 host interface. The setting of the AMC2-4R4 must correspond with the settings of the RS-232 / RS-485 converter. Figure 4.34: RS-485 host interface Figure 4.35: RS-485 host interface Figure 4.36: RS-485 host interface 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Figure 4.38: Setting of the jumpers for RS-485 two wire connections Figure 4.39: Setting of the jumpers for RS-485 two wire connections For RS-485 two wire connection, set the AMC-MUX DIL switch at positions 3, 7 and 8 to ON. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
– , page 17 4.9.2 RS-485 Four Wire Connection Figure 4.40: Connection scheme of an RS-485 four wire connection shield TxRx+ TxRx- signal ground Figure 4.41: Settings for RS-485 four wire connection 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 59
. Notice! See the notices for setting the RS-232 / RS-485 converter. Notice! If a four-wire connection is used the interface must be set up as a crosslink. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
As the AMC2 controller is conceptionally a PC, it is not possible to connect them directly using normal cables. Use instead a null modem or “crossover” cable. A complete connection diagram of the RS-232 host interface is shown in chapter Connecting Diagrams, page 102 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Figure 4.44: Location of the selector for host settings DIL Switches Address none Tab. 4.4: Setting the address via the DIL switch DIL Switches Mode SDEB RS-232 RS-485 Tab. 4.5: Protocol and connection settings Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
RS-485 host connection, provided only one AMC2 is connected on the bus Set BPA (= DIL switch 5 to OFF) in the case of an – RS-485 host connection with more than one and maximum eight AMC2s per bus 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
If using an RS-232 connection, set the address by configuring it in the Access Control System. This is a point-to-point connection that is usually configured as address 1, so set switch 1 to Figure 4.46: Location of the selector for host settings DIL Switches Address none Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
The address of the board is set using a switch on the board’s underside (see Equipment Configuration, page 16). The AMC2-4R4 is always assigned address 0. The extension boards are assigned the addresses 1 to 3. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
The AMC2-4R4 is connected to the AMC2 controller using the RS-485 extension interface. This interface will also be used to connect further extension modules. Figure 4.47: Location of the RS-485 extension module bus Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 66
| Installing Access Modular Controller 2 Figure 4.48: Location of the RS-485 extension module bus Figure 4.49: Location of the RS-485 extension module bus Figure 4.50: Location of the RS-485 extension module bus 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 67
You can find further information about the extension boards in their installation manuals. A complete connection diagram of the RS-485 extension module bus is shown in Connecting Diagrams, page 102. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Each interface is connected using a 10-pin pluggable screw - refer to Connecting Diagrams, page 102 . Figure 4.54: Location of the Wiegand interfaces for external devices Figure 4.55: Location of the Wiegand interfaces for external devices Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
If your reader requires a voltage other than 12V or is the power consumption more than 200 mA then it will require an external power supply. Notice! The list below might become obsolete. For current reader types, please refer to the Bosch Online-Catalogue. Wiegand reader type W 1...
Page 71
The Wiegand reader interface of the AMC2-4R4 does not provide sufficient power for the ARD-R90. Please plan an external power supply for the ARD-R90. Wiegand reader type W 2 This wiring diagram refers to the following readers from the BOSCH catalog: Part Number ARD-P0834-01 F.01U.028.449...
| Installing Access Modular Controller 2 Wiegand reader type W 3 This wiring diagram refers to the following readers from the BOSCH catalog: Part Number ARD-AYK12 F.01U.075.408 ARD-AYJ12 F.01U.075.388 ARD-AYH12 F.01U.075.389 ARD-AYQ12 F.01U.075.390 ARD-AYCE65B F.01U.075.391 Wiegand reader type W 4 The reader has an additional DIL switch to choose the following parameter settings.
RS-485 Host Interface, page 55 4.15 RS-232 Interface for Card Readers The AMC2-4R4 has RS-232 interface to integrate with RS-232 compatible interfaces. Each interface is connected using a pluggable screw connector . Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 74
A complete connection diagram of the RS-232 interface is shown in , page 116. Notice! A complete connection diagram of the RS-232 interface is shown in chapter Connecting Diagrams, page 102 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
- refer to chapter Connecting Diagrams, page 102. The AMC2 8I-8O-EXT has the connectors S6 - 9 and S14 - 17, only. Figure 4.61: Location of the relay output connectors Figure 4.62: Location of the relay output connectors Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 76
| Installing Access Modular Controller 2 Figure 4.63: Location of the relay output connectors Figure 4.64: Location of the relay output connectors Figure 4.65: Location of the relay output connectors 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 77
Each relay output can operate in ‘wet’ mode, using the AMC2-4W 's internal 12/24 Vdc power supply for external devices or ‘dry’ mode with potential free contacts for externally powered systems. Figure 4.68: Wet mode and dry mode of the AMC2 relay outputs Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 78
Notice! Risk of damage to equipment Do not connect externally powered devices in wet mode. This can damage the AMC2-4R4. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 79
Notice! Risk of damage to equipment Do not connect externally powered devices in wet mode. This can damage the AMC2-4W . Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 80
(D1) or wet ( D2) mode. Figure 4.71: Location of relay output jumpers (bottom side) Figure 4.72: Location of relay output jumpers (bottom side) Figure 4.73: Location of relay output jumpers Figure 4.74: Location of relay output jumpers 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 81
Access Modular Controller 2 Installing | en Notice! The positions of the jumpers 1 and 2 are interchanged related to the corresponding interfaces. Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
When connecting a relay output to an AMC2 input use dry mode with potential-free contact - refer to Connecting Relay Outputs, page 75. Figure 4.75: Location of the analog input connectors Figure 4.76: Location of the analog input connectors 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 83
Access Modular Controller 2 Installing | en Figure 4.77: Location of the analog input connectors Figure 4.78: Location of the analog input connectors Figure 4.79: Location of the analog input connectors Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 84
The extension package includes 2,2 kΩ resistors which can be used to replace R and R resistor. The AMC2-4W can also detect the wiring conditions ‘short circuit’ and ‘broken’, and hence trigger an alarm if the appropriate devices are connected. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 85
The following table shows the maximum values of permissible cable resistance depending on the used resistor combination. 1100 1100 1050 1050 1050 1100 1200 1200 1300 1300 1250 1300 1400 1500 1500 1500 1500 Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 86
For UL Access controls installations, only the R = 2k2 and R = 2k2 End-of-Line resistors may be used. Notice! We recommend using serial resistors (R ) no higher than 5K6 in order to obtain clear measurements. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
2-pin pluggable screw connector marked with T. When not in use this tamper contact should be shorted. Figure 4.81: Location of the tamper protection contact Figure 4.82: Location of the tamper protection contact Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 88
| Installing Access Modular Controller 2 Figure 4.83: Location of the tamper protection contact Figure 4.84: Location of the tamper protection contact Figure 4.85: Location of the tamper protection contact 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 89
Access Modular Controller 2 Installing | en Figure 4.86: Location of the tamper protection contact Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
The liquid crystal display delivers status information about the AMC2-4W . Push the 'Dialog' button to switch between different modes. Figure 5.1: Location of the ’Dialog’ button Figure 5.2: Location of the ’Dialog’ button Figure 5.3: Location of the ’Dialog’ button 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 91
+ = online - = offline "C" = Counter of the received data packages from the host interface. RS 485 Bus connection: A = Address 1 … H = Address 8 Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Do not use special characters or spaces. The network name must start with a letter. The names are not case sensitive. Notice! Consult the AmcIpConfig tool’s own online help for details on configuring the AMC2-4R4. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 93
Do not use special characters or spaces. The network name must start with a letter. The names are not case sensitive. Notice! Consult the AmcIpConfig tool’s own online help for details on configuring the AMC2-4W . Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
As soon as it is online again, the AMC2-4W bootloader will download a fresh copy of the application program and configuration. If the problem persists please request technical support. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 95
Access Modular Controller 2 Operating | en Figure 5.4: Resetting the AMC2 Figure 5.5: Resetting the AMC2 16I-16O-NET Figure 5.6: Resetting the AMC2-DCUA Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Subnet mask = [assigned by DHCP server or “0.0.0.0” if not available] – Password = no password Figure 5.7: Resetting the AMC2 to delivery state Figure 5.8: Resetting the AMC2-DCUA to delivery state 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Serial EEPROM – RTC (real time clock) – Pluggable Compact Flash card – Battery for SRAM and RTC – DIL switch for host settings (address and protocol mode) – Host interfaces Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 98
Output power rated maximum 2.5 A @ 10 - 14 Vdc (voltage output is dependent on board voltage input) – Tamper contact for external enclosures – Eight analog inputs with tamper detection; only connect dry contacts 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 99
0° C to 50°C (32° F to 122°F) Environment temperature 13° C to 35° C (55° F to 95° F) Humidity Up to 95%, without condensation Housing material ABS with OC (UL 94 V-0) Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 100
To determine the environmental impact of an installation, take into account the most extreme values of all participating devices. To determine the vulnerability of an installation, take into account the most restrictive values of all participating devices. 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 101
Access Modular Controller 2 Technical Data | en 101 Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Figure 7.1: Connectors on upper PCB Shield Data RxTx+ (2-wire) Data Rx+ (4-wire) Data RxTx- (2-wire) Data Rx- (4-wire) Ground (PAG) Data Tx+ (4-wire) Data Tx- (4-wire) Tab. 7.13: RS-485 host on upper PCB 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 103
Access Modular Controller 2 Appendices | en 103 TXD+ TXD- RXD+ not connected not connected RXD- not connected not connected Tab. 7.14: Ethernet Network socket (RJ45) Figure 7.2: Interconnect diagram of the RS-232 serial interface Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 104
104 en | Appendices Access Modular Controller 2 Figure 7.3: Connector blocks of the AMC2-4W 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 105
Access Modular Controller 2 Appendices | en 105 Figure 7.4: Connector blocks of the AMC2-2R2 Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 106
106 en | Appendices Access Modular Controller 2 Figure 7.5: Connector blocks of the AMC2-4R4 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 107
Access Modular Controller 2 Appendices | en 107 Figure 7.6: Connector blocks of the AMC2-DCUA Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 108
108 en | Appendices Access Modular Controller 2 Figure 7.7: Connector blocks of the AMC2-4WE 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 109
Access Modular Controller 2 Appendices | en 109 Figure 7.8: Connector blocks of the AMC2-16ION Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 110
110 en | Appendices Access Modular Controller 2 Figure 7.9: Connector blocks of the AMC2-16IOE 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 111
Access Modular Controller 2 Appendices | en 111 Figure 7.10: Connector blocks of the AMC2-8IOE Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 112
TXD- RXD+ not connected not connected RXD- not connected not connected Tab. 7.15: Ethernet Network socket (RJ45) Shield Data RxTx+ Data RxTx- Ground (PAG) Data Tx+ Data Tx- Tab. 7.16: RS-485 host 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 113
Card Present Tab. 7.18: Wiegand interface AMC Reader Supply (12V) black Reader Supply (0V) green Data 0 white Data 1 (Clock) purple Shield brown green LED Tab. 7.19: Wiegand interface W2 Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 114
Reader Supply (8V - 30V)DC Tab. 7.21: Wiegand interface W4 Notice! For reader settings refer to the respective reader manual. Reader Supply (12V) Reader Supply (0V) Data Data clock Shield green LED red LED Beeper 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 115
Access Modular Controller 2 Appendices | en 115 Hold Card Present Tab. 7.22: Omron interface Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 116
Data TxD Data RxD Tab. 7.25: RS-232 interface Analog Input, in Analog Input, out Tab. 7.26: Analog input Relay Output, normally open Relay Output, common Relay Output, normally closed Tab. 7.27: Relay output 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 117
Power supply for external devices (10V - 30V) Power supply for external devices (0V) Shield Data RxTx+ Data RxTx- Ground (PAG) Tab. 7.28: Host / Extension interface Tamper Contact, in Tamper Contact, out Tab. 7.29: External tamper contact Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...
Page 118
118 en | Appendices Access Modular Controller 2 2020-01 | V02 | Installation manual Bosch Access Systems V.B.
Page 119
Access Modular Controller 2 Appendices | en 119 Bosch Access Systems V.B. Installation manual 2020-01 | V02 |...