Access Modular
Controller
4.11
DIL switch selector
4.11.1
Host settings
DIL switches are used to configure the host settings. The first
four DIL switches for address selection define the RS-485
address of the AMC2 in a RS-485 bus system. Switch 5 selects
one of the two different protocols, SDEB and BPA (according to
DIN6619).
Switch 6 sets the connection to the host system to either
RS-232 or RS-485.
Notice!
If using an Ethernet connection, set switch 1 to ON (= factory
setting).
If using an RS-232 connection, set the address by configuring it
in the Access Control System. This is a point-to-point
connection that is usually configured as address 1, so set
switch 1 to ON.
Figure 4.14: Location of the selector for host settings
Bosch Sicherheitssysteme
Installing | en
35
2016-11 | AMC2-4W |