Access Modular Controller 2
Figure 3.6: Jumper at the bottom side
3.3

Performance Characteristics

Bosch Security Systems B.V.
19
Jumper for setting either voltage free relay output ("dry" mode) or looped-in voltage
from the AMC2 internal power supply ("wet" mode).
20
Jumper: Potential equalization between different systems and earth ground (shield)
for the bus systems.
21
Jumper: Equalization of potential between different systems and earth ground
(shield) for the extension interface.
Intelligent access manager for 1 - 8 entrances (for example doors, man traps, barriers)
Host address selectable using DIL sliding switch.
Four possible configurable host interfaces:
Ethernet (= standard)
RS-485 2-wire
RS-485 4-wire
RS-232
Reader interfaces
four RS-485 interfaces
8 relay outputs
voltage free, power is supplied externally (dry mode)
powered by internal power supply (wet mode)
8 analog inputs with internal power supply
Battery buffered SRAM and real time clock (RTC)
Pluggable Compact Flash card
Liquid Crystal Display
Transfer rate host interface RS-485: 38,4 kBit/s
Transfer rate host interface RS-232: 38,4 kBit/s
Transfer rate host interface Ethernet: 10/100 Mbit/s
Transfer rate to the extension interface: 9,6 kBit/s
Transfer rate reader interface RS-485: 9,6 kBit/s
Self regulating transmit/receive switching
Supply voltage: 10 V to 14 Vdc,
Max current load: 3A
Tamper contact for external covers