SETTING THE MODBUS ADDRESS

Press the SETUP key again and the
LCD will display the Modbus
communications address. The factory
default is 01. The Z-2000-T has
integrated Modbus communications
capability for remote monitoring and
control. For more information on Modus
Communications, contact Jackson
Systems at 1-888-652-9663 or
info@jacksonsystems.com. (Figure 10)
FIGURE 10
TEMPERATURE CALIBRATION
OFFSET
Press the SETUP key again and the
LCD will display the temperature
calibration offset. The factory default
setting is 0. Typically, it is not necessary
to adjust the temperature calibration
offset as the Z-2000-T has been factory
calibrated. If calibration is necessary, a
high quality electronic digital
thermometer must be used. Place the
thermometer sensor probe next to the
thermostat sensor and allow five
minutes before comparing the
temperature readings. Use the UP and
DOWN keys to adjust the temperature
calibration. The range is +/- 9° F.
(Figure 11)
8
FIGURE 11
SENSOR
LOCATION
www.jacksonsystems.com
1.888.652.9663