Jackson Systems Wireless Comfort WCT-32 Installation Manual

Jackson Systems Wireless Comfort WCT-32 Installation Manual

7-day programmable, battery powered thermostat
Hide thumbs Also See for Wireless Comfort WCT-32:

Advertisement

Quick Links

Wireless
COMF RT
Made in the USA

Specifications

Compatible Equipment
Output Terminals
Fan Operation
LED Indicator
Communications
Range
Control Module Power
Control Module Housing
Control Module Dimensions
Thermostat Dimensions
TM
Application
SY ST EM
FA N
Features
Single stage, multi-stage and heat pumps (3 heat / 2 cool)
W1/B, O, W2/E, Y1, Y2, G
Gas or electric
Multi-color indicates heating, cooling and fan calls
Wireless, 915MHz, proprietary protocol
Up to 100 feet
24VAC, 2.4VA
Molded plastic
5.09 x 2.65 x 1.10 inches (WHD)
5.00 x 4.50 x 1.00 inches (WHD)
Installation Manual
Model WCT-32
The WCT-32 is a 7-day programmable, battery
powered thermostat that communicates via an
RF wireless data link to a relay control module
located near the HVAC equipment.
The WCT-32 can control single stage, multi-
stage and heat pumps with up to 3 stages of
heating and 2 stages of cooling.
Manual or programmable selection with up
to four schedules per day.
Exclusive Memory Backup insures reliable
performance in the event of a
communications interruption.
Wireless 915MHz proprietary protocol with
up to 100' transmission range.
Easy access, front-loading battery
compartment. 2 AA batteries included.

Advertisement

Table of Contents
loading

Summary of Contents for Jackson Systems Wireless Comfort WCT-32

  • Page 1: Specifications

    Installation Manual COMF RT Model WCT-32 Made in the USA Application The WCT-32 is a 7-day programmable, battery powered thermostat that communicates via an RF wireless data link to a relay control module located near the HVAC equipment. SY ST EM...
  • Page 2: Installation

    2.65” HVAC Module .187” dia. 2 plcs Installation The HVAC module should be installed close to 5.09” the equipment being controlled. Do not install it 4.57” within a metal enclosure that might interfere with wireless communications. Only standard 18 gauge thermostat wire is required to wire the module to the equipment.
  • Page 3: Installing The Sub-Base

    Thermostat Installing the Sub-Base The thermostat should be installed approximately Location 5 feet above the floor. The thermostat should be located in an area that Level the sub-base for appearance and use the represents the ambient space temperature and wall anchors and screws provided. within 100 feet of the HVAC Control Module.
  • Page 4: Thermostat Installer Options

    Installer Options Chart Option Description Thermostat Installer Options Zone number Range 01 to 08 Default The installer options can be accessed by Home number pressing and holding the ENTER key for seven Range 01 to 32 Default seconds. The LCD displays Option 01 for setting Program HVAC module with Zone number.
  • Page 5: Selecting Equipment Type

    The LCD display for Option 03 is shown below. Use the Down keys to set the Home Press the ENTER key to send the new address to number for the thermostat. The Home number the HVAC module after pressing the module can be set from 01 to 32.
  • Page 6: Minimum Off Time

    Set To Heating Setpoint Limit The maximum heating setpoint the user can set is 60 to 85F. Press the NEXT key to select Option 08 press the key to set maximum Down Option allowable heating setpoint. CANCEL NEXT ENTER Set To Minimum Off Time The minimum Off time prevents the compressor from restarting too quickly.
  • Page 7: First Stage Differential

    Press the key to select and the Press the key to select NEXT Option 12 NEXT Option 11 Down key to set the second stage press the Down key to set the setpoint temperature differential. If the first stage differential. temperature differential is greater than third stage temperature differential, first stage differential will automatically be incremented.
  • Page 8: Automatic Backup

    Due to ongoing product improvements, Jackson Typically, it is not necessary to adjust the Systems reserves the right to change the specifications of the WCT-32 thermostat or its temperature calibration offset from the factory components without notice. setting. If calibration is necessary, a high quality electronic digital thermometer must be used.

Table of Contents