OVERRIDE TO OPEN
Press the UP and DOWN keys until the
word OPEN appears on the LCD and
then press the ENTER key. The damper
will drive open and remain in the open
position until the override is cancelled.
(Figure 18)
FIGURE 18
OVERRIDE TO CLOSE
Press the UP and DOWN keys until the
word CLOSED appears on the LCD and
press the ENTER key. The damper will
drive closed and remain in the closed
position until the override is cancelled.
(Figure 19)
FIGURE 19
CANCELLING THE DAMPER
OVERRIDE
In order for the Z-2000-T to control normal
damper operation, the override must be
cancelled. Press and hold the SETUP key
until the word DAMPER OPEN or
DAMPER CLOSE appears on the LCD.
Use the UP or DOWN key until only the
word DAMPER is displayed and then
press the ENTER key. The thermostat will
then resume normal operation. Figure 20)
Z-2000-T SPECIFICATIONS
Input Voltage
Relay Rating
Operating Temperature
Operating RH
Size
LCD Display Size
Temperature Sensor
Accuracy
Display Resolution
Control Range
Back Light
Back Light Life
Communications Protocol
Approvals
Warranty
11
FIGURE 20
24 VAC 50/60 Hz
24 VAC @ 1Amp per relay
23° F to 122° F
0-95% (non-condensing)
4-7/16" W x 4-1/16" H x 7/8" D
2-3/4" W x 1-7/8" H
10K NTC type 3
+/- 1° F @ 77° F
1° F
36° F to 96° F
Blue EL (Electro Luminescent)
3,000 hours to half brightness
Modbus
FCC (Part 15) (Pending) C-tick
5 years
06-1050-051410
www.jacksonsystems.com
1.888.652.9663