Daikin ETSHB16P30EF Installer's Reference Manual page 46

Hide thumbs Also See for ETSHB16P30EF:
Table of Contents

Advertisement

6
|
Application guidelines
Installer reference guide
46
c Mixing valve station
d Pressure regulating valve (field supply)
e Safety thermostat (field supply)
f Bizone kit control box (EKMIKPOA)
g Bypass valve
h Hydraulic separator (balancing bottle)
i Direct pump (for additional zone) (e.g. unmixed pump group EKMIKHUA)
INFORMATION
A pressure regulating valve should be implemented before the mixing valve station.
This is to guarantee the correct water flow balance between the main leaving water
temperature zone and the additional leaving water temperature zone in relation to
the required capacity of both water temperature zones.
A bypass valve must be installed to make water recirculation possible when all
shut-off valves are closed. To guarantee reliable operation, provide a minimum
water flow as described in table "To check the water volume and flow rate" in
"8.1 Preparing water
For the main zone:
-
The mixing valve station (including pump + mixing valve) is installed before the
underfloor heating.
-
The mixing valve station is controlled by the bizone kit controller (EKMIKPOA)
based on the heating request of the room.
-
The room temperature is controlled by the dedicated Human Comfort
Interface (BRC1HHDA used as room thermostat).
-
Ensure water circulation is possible in main zone when shut-off valves are
closed
-
In cooling mode, you can allow the underfloor heating (main zone) to provide
refreshment (no real cooling), or NOT allow it.
If allowed:
Do NOT install a shut-off valve.
Set [F-0C]=0 to activate the setpoint screen of [2] Main zone and [1] Room.
Set the leaving water temperature of the main zone NOT too low (typically:
20°C)
If NOT allowed, install a shut-off valve (field supply) and connect it to X12M/18
and X12M/14 for a normally open valve or X12M/18 and X12M/13 for a
normally closed valve.
For the additional zone:
-
The heat pump convectors are directly connected to the indoor unit.
-
The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat
pump convectors. For more information, see:
The installation manual of the heat pump convectors
The installation manual of the heat pump convector options
The addendum book for optional equipment
-
The heating or cooling demand signals of each heat  pump convector are
connected in parallel to the digital input on the indoor unit (X12M/19 and
X12M/22). The indoor unit will only supply the desired additional leaving water
temperature when there is an actual demand.
4
piping" [
 86].
EPRA14~18DAV3+W1 + ETSH/X(B)16P30+50EF
Daikin Altherma 3 H HT ECH₂O
4P679467-1 – 2022.02