9
|
Electrical installation
Installer reference guide
122
CAUTION
To guarantee the unit is completely earthed, ALWAYS connect the backup heater
power supply and the earth cable.
The backup heater capacity is depending on the chosen BUH option kit. Make sure
that the power supply is in accordance with the backup heater capacity, as listed in
the table below.
Backup heater
Backup
type
capacity
*3V
*6V
*9W
(a)
Electrical equipment complying with EN/IEC 61000-3-12 (European/International Technical
Standard setting the limits for harmonic currents produced by equipment connected to
public low-voltage systems with input current >16 A and ≤75 A per phase).
(b)
This equipment complies with EN/IEC 61000‑3‑11 (European/International Technical
Standard setting the limits for voltage changes, voltage fluctuations and flicker in public
low-voltage supply systems for equipment with rated current ≤75 A) provided that the
system impedance Z
supply and the public system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a system impedance Z
equal to Z
.
max
Connect the backup heater power supply as follows:
Power supply
heater
1 kW
1N~ 230 V
2 kW
1N~ 230 V
3 kW
1N~ 230 V
2 kW
1N~ 230 V
4 kW
1N~ 230 V
6 kW
1N~ 230 V
3 kW
3N~ 400 V
6 kW
3N~ 400 V
9 kW
3N~ 400 V
is less than or equal to Z
sys
max
Maximum
running current
4.4 A
8.7 A
13.1 A
8.7 A
(a)(b)
17.4 A
(a)(b)
26.1 A
4 A
9 A
13 A
at the interface point between the user's
sys
EPRA14~18DAV3+W1 + ETSH/X(B)16P30+50EF
Daikin Altherma 3 H HT ECH₂O
4P679467-1 – 2022.02
Z
max
0.22 Ω
0.22 Ω
less than or