10
|
Configuration
Installer reference guide
180
#
Code
[3.6]
[0-04]
[0-05]
[0-06]
[0-07]
Emitter type
For more information about Emitter type, see
#
Code
[3.7]
[2‑0D]
The setting of the emitter type has an influence on the space heating setpoint
range and the target delta T in heating as follows:
Emitter type
Additional zone
0: Underfloor
heating
1: Fancoil unit
2: Radiator
Set weather-dependent cooling:
T t
[0-05]
[0-04]
[0-07]
T
:
Target
leaving
t
(additional zone)
T
: Outdoor temperature
a
[0-07]: Low outdoor ambient temperature.
10°C~25°C
[0-06]: High outdoor ambient temperature.
25°C~43°C
[0-05]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
[9‑07]°C~[9‑08]°C
Note: This value should be higher than [0‑04]
as for low outdoor temperatures less cold
water is required.
[0-04]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
[9‑07]°C~[9‑08]°C
Note: This value should be lower than [0‑05] as
for high outdoor temperatures colder water is
required.
"10.5.3 Main
Emitter type:
0: Underfloor heating
1: Fancoil unit
2: Radiator
Space heating setpoint
range [9‑05]~[9‑06]
Maximum 55°C
Maximum 55°C
Maximum 70°C
Description
[0-06]
T a
water
temperature
ambient
temperature.
ambient
temperature.
4
zone" [
 167].
Description
Target delta T in heating
[1‑0C]
Variable (see [3.B.1])
Variable (see [3.B.1])
Fixed 10°C
EPRA14~18DAV3+W1 + ETSH/X(B)16P30+50EF
Daikin Altherma 3 H HT ECH₂O
4P679467-1 – 2022.02