Daikin ETSHB16P30EF Installer's Reference Manual page 190

Hide thumbs Also See for ETSHB16P30EF:
Table of Contents

Advertisement

10
|
Configuration
Installer reference guide
190
[9-0D]=4/8
a (kPa)
a External static pressure
b Water flow rate
Pump outside range
When the pump operation function is disabled the pump will stop if the outdoor
temperature is higher than the value set by the Space
temperature [4‑02] or if the outdoor temperature drops below the value set by
the Space cooling off temperature [F‑01]. When the pump operation is
enabled, the pump operation is possible at all outdoor temperatures.
#
Code
[4.9]
[F-00]
Increase around 0°C
Use this setting to compensate for possible heat losses of the building due to the
evaporation of melted ice or snow. (e.g. in cold region countries).
In heating operation, the desired leaving water temperature is locally increased
around an outdoor temperature of 0°C.This compensation can be selected when
using an absolute or a weather dependent desired temperature (see illustration
below).
T
T
t
t
L
R
T
A
0°C
a
a Absolute desired LWT
b Weather dependent desired LWT
#
Code
[4.A]
[D-03]
b (l/min)
Pump operation:
0: Disabled if outdoor temperature is higher
than [4‑02] or lower than [F‑01] depending on
heating/cooling operation mode.
1: Possible at all outdoor temperatures.
L
R
T
A
0°C
b
Increase around 0°C:
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
heating
Description
Description
EPRA14~18DAV3+W1 + ETSH/X(B)16P30+50EF
Daikin Altherma 3 H HT ECH₂O
4P679467-1 – 2022.02
off

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents