System Sensor FAAST LT-200 Setup Manual page 18

Hide thumbs Also See for FAAST LT-200:
Table of Contents

Advertisement

EXAMPLE PIPE CONFIGURATIONS USING EXTERNAL FILTER
5
Hole 1
3
FILTER
FAN
SPEED
= 9
FILTER
3
FAN
SPEED
= 9
3
FILTER
FAN
SPEED
= 10
D200-100-01
Example Pipe Configuration 1 Channel Single Pipe
6
6
Hole 2
Hole 3
HOLE
1
2
SIZE (mm)
3.5
3.5
3.5
Example Pipe Configuration
7
12
Hole 1
HOLE
1
2
SIZE (mm)
4
4.5
Example Pipe Configuration
34
HOLE
1
END
SIZE (mm)
6.5
6.5
With Filter - Class C
Flow = 43 l/min, Balance = 0.72, Alarm level 1
47m
6
6
Hole 5
Hole 4
6
7
3
4
5
3.5
3.5
3.5
3.5
47m
7
Hole 2
Hole 3
3
4
5
END
4.5
5.5
6.5
5
47m
18
6
6
Hole 6
Hole 7
END
3.5
1 Channel Single Pipe
With Filter - Class B
Flow = 44 l/min, Balance = 0.7, Alarm level 1
7
7
Hole 5
Hole 4
1 Channel Single Pipe
With Filter - Class A
Flow = 36 l/min, Balance = 0.91, Alarm level 1
Hole 1
6
End hole
(Hole 8)
7
End hole
(Hole 6)
13
End hole
(Hole 2)
I56-3888-010

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FAAST LT-200 and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF