System Sensor D4P120 Installation Instructions Manual

System Sensor D4P120 Installation Instructions Manual

Smoke detector kits

Advertisement

Quick Links

Litho U.S.A.
E2015
Installation INSTRUCTIONS FOR SMOKE DETECTOR KITS
(11K76 & 11K80; 603408-09 & 603408-10) USED WITH KC/KG/KH/LC/LG092 - 152 UNITS

Shipping and Packing List

Supply OR Return Air Applications
11K76 single-sensor kit contains the following:
1 - Smoke detector sensor
1 - Smoke detector power board
2 - Supply brackets
1 - Hinged panel
1 - Hinged panel mounting bracket
1 - Panel holder
1 - Power harness (J255/1, 4 -- used on KC, KG & KH
units only)
1 - Power harness (J255/J262 -- used on LG & LC units
only)
1 - Supply harness (P253/P252)
1 - Return harness (P250/P251)
1 - Jumper harness (P250/J261 --used on supply air SD
units only)
1 - 36" metal sampling tube (used on supply air SD units
only)
1 - 18" metal sampling tube (used on return air SD units
only)
1 - Plastic exhaust tube
1 - Magnet
1 - Sensor manufacturer's instructions
#10 - 16 X 3/4" sheet metal screws
#8 - 32 X 1" thread-forming screws
#8 - 32 X 1/2" thread-forming screws
Insertion-type wire ties
WARNING
Improper installation, adjustment, alteration, ser­
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser­
vice must be performed by a licensed professional
installer, service agency or the gas supplier.
PACKAGED UNITS KITS
AND ACCESSORIES
506437-01
1/2015
SMOKE DETECTOR KITS
Supersedes 10/2012
Supply AND Return Air Applications
11K80 dual-sensor kit contains the following:
2 - Smoke detector sensors
1 - Smoke detector power board
2 - Supply brackets
1 - Hinged panel
1 - Hinged panel mounting bracket
1 - Panel holder
1 - Power harness (J255/1,4 -- used on KC, KG & KH
units only)
1 - Power harness (J255/J262 -- used on LG & LC units
only)
1 - Supply harness (P253/P252 -- used on KC, KG & KH
units only)
1 - Return harness (P250/P251)
1 - 36" metal sampling tube (used on supply air SD units
only)
1 - 18" metal sampling tube (used on return air SD units
only)
2 - Plastic exhaust tubes
2 - Magnets
1 - Sensor manufacturer's instructions
#10 - 16 X 3/4" sheet metal screws
#8 - 32 X 1" thread-forming screws
#8 - 32 X 1/2" thread-forming screws
Insertion-type wire ties
Danger of sharp metallic edges. Can cause injury.
Take care when servicing unit to avoid accidental
contact with sharp edges.

Application

Lc And Lg Units -- Smoke detector will send a 24Vac
signal to the unit controller when smoke is sensed. The
unit controller default mode will de-energize unit.
Kc, Kg And Kh Units -- Smoke detector will interrupt the
24Vac signal to the unit control circuit when smoke is
sensed. Unit will be de-energized.
Page 1
D4P120 & D4S
CAUTION

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the D4P120 and is the answer not in the manual?

Questions and answers

Summary of Contents for System Sensor D4P120

  • Page 1 PACKAGED UNITS KITS AND ACCESSORIES Litho U.S.A. E2015 D4P120 & D4S 506437-01 1/2015 SMOKE DETECTOR KITS Supersedes 10/2012 INSTALLATION INSTRUCTIONS FOR SMOKE DETECTOR KITS (11K76 & 11K80; 603408-09 & 603408-10) USED WITH KC/KG/KH/LC/LG092 - 152 UNITS Supply AND Return Air Applications...
  • Page 2 Sampling tube installation Installation 1 - Select the appropriate sampling tube. CAUTION Supply air sensor -- 36” Return air sensor -- 18” Before attempting to perform any service or mainte­ 2 - Slide metal sampling tube onto the back side of the nance, turn the electrical power to unit OFF at dis­...
  • Page 3 SMOKE DETECTOR SENSOR WITH SAMPLING TUBE AND EXHAUST TUBE PLASTIC EXHAUST TUBE METAL SAMPLING TUBE (Point sampling holes toward air stream) SENSOR HEAD MAGNET TEST LOCATION FIGURE 3 Wiring KC, KG & KH CONTROLS AREA IDENTIFY CONNECTORS ROUTE P253 TO BY LABELS STAMPED SUPPLY AIR SENSOR GROUND TAB...
  • Page 4 KC, KG and KH Units #8-32X1” screws. Route power board harness behind hinged panel as shown in figure 5 using 1 - Supply air smoke detector installations -- Route provided insertion-type wire ties. harness wires across the top of the unit. Secure wires 5 - Use two #8 - 32 X 1/2”...
  • Page 5 KC, KG or KH Unit Application with Single Return Air Smoke Detector (Note: Verify that power board DIP switch is set to 1) 53W80 Kit harness connections shown in bold. 6 PIN 6 PIN 4 Wires J255 P255 A173 SMOKE Wires marked DETECTOR 4 PIN...
  • Page 6 KC, KG or KH Unit Application with Return Air and Supply Air Smoke Detectors (Note: Change power board DIP switch setting to 2) Kit harness connections 53W81 shown in bold. 6 PIN 6 PIN A173 4 Wires J255 P255 SMOKE Wires marked Wires marked DETECTOR...
  • Page 7 LC and LG Units Test Magnet(s) 1 - Install power board and hinged panel in control box A test magnet is provided in a bag assembly with each as outlined in steps 4 through 7 in KC, KG and KH sensor.
  • Page 8 LC or LG Unit Application with Single Supply Air Smoke Detector (Note: Verify that power board DIP switch is set to 1) 53W80 Kit harness connections shown in bold. Wires marked Wires marked J262C-1, 2, 2, or 3 J255-1, 2, 3, or 6 6 PIN 6 PIN J262C...