6.4.7. Regeneration flow
Set the direction of flow during the brine draw cycle.
A
Note
The availability depends on the valve type programmed in the previous step.
Options:
•
Co-current;
•
Counter-current;
•
Counter-current dry salt.
N
Set regeneration flow with
→ Default setting: Co-current
O
Press
to validate the selection and advance to the next
parameter.
6.4.8. Remote started regeneration
Start a regeneration from an external signal (see chapter 5.9. Connections (electrical), page 46).
A
Note
The regeneration starts immediately after the closure of the contact which timing is set. A
closure time is requested to validate the signal before the regeneration start.
A
Note
This mode can be combined with the other methods of regeneration, it has priority once it is
activated.
P
Set the remote controller with
→ Can be adjusted from 00:00:01 to 01:39:00.
Q
Press
to validate the selection and advance to the next
parameter.
Ref. MKT-IM-002 / A - 18.11.2016
Installer Manual Fleck 2910 - NXT - Programming
and
.
,
and
.
REGENERATION IN
CO-CURRENT
Without remote controller
REMOTE SIGNAL
START:NO
With remote controller and 1
minute contact programmed
REMOTE SIGNAL
START:
00:01:00
55 / 98