Valve Connection To Piping - Pentair FLECK 2910 NXT Installer Manual

Hide thumbs Also See for FLECK 2910 NXT:
Table of Contents

Advertisement

5.7.6.2 System operation in regeneration
Inlet
Valve
Tank
Full capacity
4th in standby
If two tanks are in service and both reach Volume remaining = 0, the other two tanks will shift from
standby into service. The lead tank with Volume remaining = 0 will start regeneration. The second tank
with Volume remaining = 0 will enter into standby. If the flow increases past the trip point, a third tank
needs to enter in service. The tank in standby with Volume remaining = 0 will shift into service to
maintain a steady flow. Operating for extended periods in this mode may degrade the water quality.
5.8.

Valve connection to piping

The connections should be sealed using PTFE (plumber's tape) on the threads if using the threaded
connection type.
In case of heat welding (metal type connection), the connections should not be made to the valve when
soldering.
A
Note
See chapter 3.3. Components description and location, page 15 to identify the connections.
Ref. MKT-IM-002 / A - 18.11.2016
Meter
Meter
Valve
Tank
¾ capacity
3rd in standby
programmed rate
Installer Manual Fleck 2910 - NXT - Installation
Meter
Valve
Valve
Tank
Tank
½ capacity
¼ capacity
First trip point
New primary
tank
Outlet
Meter
45 / 98