3 Electrical Installation
S1
Terminal A2 Signal Selection
S2
RS422/485 Termination Resistor
Safe Disable Input
S3
Sink/Source/External Supply Selection
S4
Terminal A3 Analog/PTC Input Selection
S5
Terminal FM/AM Signal Selection
Control Circuit Terminal Functions
Type
No.
Multi-function input 1 (Closed: Forward run,
S1
Open: Stop)
Multi-function input 2 (Closed: Reverse run,
S2
Open: Stop)
Multi-function input 3 (External fault, N.O.)
S3
Multi-function input 4 (Fault reset)
S4
Multi-function input 5 (Multi-step speed
S5
reference 1)
Multi-Function
Digital Inputs
Multi-function input 6 (Multi-step speed
S6
reference 2)
Multi-function input 7 (Jog reference)
S7
Multi-function input 8 (External baseblock)
S8
Multi-function input common
SC
SN
Multi-function input 0 V
SP
Multi-function input 24 Vdc
Safe Disable input 1
H1
Safe Disable
Safe Disable input 2
H2
Inputs
Safe Disable function common
HC
EN 16
Terminal Name (Function)
YASKAWA Europe TOEP_C710606_97A - AC Drive A1000 IP54READY - Quick Start Guide
V
Current
Source
PTC
AI
Analog Input
FM
AM
FM/AM: Voltage Output
Function (Signal Level) Default Setting
Photocoupler
24 Vdc, 8 mA
Use the wire link between terminals SC and SN or SC and SP to select
between sinking, sourcing mode, and the power supply.
24 Vdc power supply for digital inputs, 150 mA max (if no digital
input option DI-A3 is used)
Never short terminals SP and SN as doing so will damage the drive.
24 Vdc, 8 mA
One or both open: Drive output disabled
Both closed: Normal operation
Internal impedance: 3.3 kΩ
Off time of at least 1 ms
Disconnect the wire jumpers shorting terminals H1, H2, and HC to
use the Safe Disable inputs. Set the S3 jumper to select between
sinking, sourcing mode, and the power supply.
Safe disable function common
I
V
I
Voltage
On
Off
External 24 Vdc
Sink
Power Supply
PTC
AI
PTC Input
V
V
I
I
FM
AM
FM: Current Output
AM: Voltage Output