Download Print this page

YASKAWA CIMR-AC4A WAA Series Quick Start Manual page 13

Hide thumbs Also See for CIMR-AC4A WAA Series:

Advertisement

Wiring Specification
Main Circuit
Use the fuses and line filters listed in the table below when wiring the main circuit. Make sure not to exceed the given
tightening torque values.
Model
EMC Filter
CIMR-A
[Block]
4A0044
FB-40060A
4A0058
4A0072
FB-40072A
4A0088
FB-40105A
4A0103
4A0139
FB-40170A
4A0165
Tightening Torque Values
Tighten the main circuit terminals using the torque values provided by the table below.
Terminal Size
Tightening Torque (Nm)
Control Circuit
The control terminal board is equipped with screwless terminals. Always use wires within the specification listed below.
For safe wiring it is recommended to use solid wires or flexible wires with ferrules. The stripping length respectively
ferrule length should be 8 mm.
Flexible with ferrule
EMC Filter Installation
This drive has been tested in accordance with European standards EN61800-3. In order to comply to the EMC standards,
wire the main circuit as described below.
1. Install an appropriate EMC noise filter to the input side. See the table in
Technical Manual for details.
2. Place the drive and EMC noise filter in the same enclosure.
3. Use braided shield cable for the drive and motor wiring.
4. Remove any paint or dirt from ground connections for minimal ground impedance.
5. Prepare braided ground strap with ring terminal to ensure proper EMC grounding from the drive to the panel.
6. Use M6 stud on drives mounting frame to connect with braided ground strap to metal mounting plate of the panel.
7. Keep this EMC grounding braided strap as short as possible.
YASKAWA Europe TOEP_C710606_97A - AC Drive A1000 IP54READY - Quick Start Guide
Main Fuse
[Bussmann]
FWH-250A
FWH-350A
FWH-400A
M5
2.0 to 2.5
Wire Type
Solid
Flexible
Recom.
R/L1,S/L2,T/L3,
Motor cable
U/T1,V/T2,W/T3,
(mm
)
2
– , +1, +2
M6
16
25
M8
35
50
M10
70
M6
4.0 to 6.0
Main Circuit on page 13
3 Electrical Installation
Main Circuit Terminal Sizes
+3
B1, B2
M5
M8
M10
M8
9.0 to 11.0
18.0 to 23.0
Wire size (mm
2
)
0.2 to 1.5
0.2 to 1.0
0.25 to 0.5
or refer to the
M8
M10
M10
EN 13

Advertisement

loading