Daikin ERGA06EAV3H Installer's Reference Manual page 296

Hide thumbs Also See for ERGA06EAV3H:
Table of Contents

Advertisement

12/12
Field settings table
Breadcrumb
Field code
Setting name
9.I
[E-07]
What kind of DHW tank is installed?
9.I
[E-08]
Power saving function for outdoor unit.
9.I
[E-09]
--
9.I
[E-0B]
Is a bi-zone kit installed?
9.I
[E-0C]
What bizone system type is installed?
9.I
[E-0D]
Is the system filled with glycol ?
9.I
[E-0E]
--
9.I
[F-00]
Pump operation allowed outside range.
9.I
[F-01]
Above which outdoor temperature is cooling allowed?
9.I
[F-02]
--
9.I
[F-03]
--
9.I
[F-04]
--
9.I
[F-05]
--
9.I
[F-06]
Enable Tank Boiler?
9.I
[F-07]
Efficiency calculation
9.I
[F-08]
Continuous heating defrost enable
9.I
[F-09]
Pump operation during flow abnormality.
9.I
[F-0A]
--
9.I
[F-0B]
Close shut-off valve during thermo OFF?
9.I
[F-0C]
Close shut-off valve during cooling?
9.I
[F-0D]
What is the pump operation mode?
9.I
[F-0E]
Tank heating support_max
Bi-zone kit settings
9.P.1
[E-0B]
Bi-zone kit installed
9.P.2
[E-0C]
Bi-zone system type
9.P.3
[7-0A]
Add zone pump fixed PWM
9.P.4
[7-0B]
Main zone pump fixed PWM
9.P.5
[7-0C]
Mixing valve turning time
4P681207-1 - 2021.12
Range, step
Default value
R/W
0~8
0 OSO tank 150/180
1 FS with BUH
2 FS with BSH
3 OSO tank 200/250/300
4 Rotex without BSH (HYB)
5 Rotex with BSH
6 Third party tank for HYB
7 Third party tank, coil >= 1,05m2
8 Third party tank, coil >= 1,8m2
R/W
0: No
1: Yes
1
R/W
0: not installed
1: -
2: Bizone kit installed
R/W
0: Without hydraulic separator / no
direct pump
1: With hydraulic separator / no direct
pump
2: With hydraulic separator / with direct
pump
R/W
0: No
1: Yes
0
R/W
0: Restricted
1: Allowed
R/W
10~35°C, step: 1°C
20°C
3
5
0
0
R/W
0: Disabled
1: Enabled
R/W
0: Enabled
1: Disabled
R/W
0: Disabled
1: Enabled
R/W
0: Disabled
1: Enabled
0
R/W
0: No
1: Yes
R/W
0: No
1: Yes
R/W
0: Continuous
1: Sample
2: Request
R/W
10~35 kW, step: 1kW
20 kW
R/W
0: not installed
1: -
2: Bizone kit installed
R/W
0: Without hydraulic separator / no
direct pump
1: With hydraulic separator / no direct
pump
2: With hydraulic separator / with direct
pump
R/W
20~95%, step 5%
95%
R/W
20~95%, step 5%
95%
R/W
20~300 sec, step 5 sec
125 sec
(*6) *EKECBUA3V*_(*7) *EKECBUA6V*_(*8) *EKECBUA9W*_(*9) BUH less_
Installer setting at variance with
default value
Date
Value
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*10) 04P_(*11) 08P