Daikin ERGA06EAV3H Installer's Reference Manual page 295

Hide thumbs Also See for ERGA06EAV3H:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
9.I
[9-0D]
Pump speed limitation
9.I
[9-0E]
--
9.I
[C-00]
Domestic heating water priority.
9.I
[C-01]
--
9.I
[C-02]
Is an external backup heat source connected?
9.I
[C-03]
Bivalent activation temperature.
9.I
[C-04]
Bivalent hysteresis temperature.
9.I
[C-05]
What is the thermo request contact type for the main zone?
9.I
[C-06]
What is the thermo request contact type for the add. zone?
9.I
[C-07]
What is the unit control method in space operation?
9.I
[C-08]
Which type of external sensor is installed?
9.I
[C-09]
What is the required alarm output contact type?
9.I
[C-0A]
--
9.I
[C-0B]
--
9.I
[C-0C]
--
9.I
[C-0D]
--
9.I
[C-0E]
--
9.I
[D-00]
Which heaters are permitted if prefer. kWh rate PS is cut?
9.I
[D-01]
Contact type of preferential kWh rate PS installation?
9.I
[D-02]
Which type of DHW pump is installed?
9.I
[D-03]
Leaving water temperature compensation around 0°C.
9.I
[D-04]
Is a demand PCB connected?
9.I
[D-05]
Is the pump allowed to run if prefer. kWh rate PS is cut?
9.I
[D-07]
Is a solar kit connected?
9.I
[D-08]
Is an external kWh meter used for power measurement?
9.I
[D-09]
Is an external kWh meter used for power measurement, kWh meter used for smart
grid?
9.I
[D-0A]
--
9.I
[D-0B]
--
9.I
[D-0C]
--
9.I
[D-0D]
--
9.I
[D-0E]
--
9.I
[E-00]
Which type of unit is installed?
9.I
[E-01]
Which type of compressor is installed?
9.I
[E-02]
What is the indoor unit software type?
9.I
[E-03]
What is the number of backup heater steps?
9.I
[E-04]
Is the power saving function available on the outdoor unit?
9.I
[E-05]
Can the system prepare domestic hot water?
9.I
[E-06]
--
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*6) *EKECBUA3V*_(*7) *EKECBUA6V*_(*8) *EKECBUA9W*_(*9) BUH less_
(*10) 04P_(*11) 08P
Range, step
Default value
R/W
0~8, step:1
0 : No limitation
1~4 : 90~60% pump speed
5~8 : 90~60% pump speed during
sampling
6 80% pump speed
6
R/W
0: Solar priority
1: Heat pump priority
0
R/W
0: Off
1: Direct (SH)
2: Indirect (DHW) (*3)
3: Indirect (DHW + SH)
R/W
-25~25°C, step: 1°C
0°C
R/W
2~10°C, step 1°C
3°C
R/W
1: 1 contact
2: 2 contacts
R/W
1: 1 contact
2: 2 contacts
R/W
0: Leaving water
1: External room thermostat
2: Room thermostat
R/W
0: No
1: Outdoor
2: Room
R/W
0: Abnormal
1: Normal
0
0
0
0
0
R/W
0: None
1: BSH only
2: BUH only
3: All
R/W
0: No
1: Open
2: Closed
3: Smart Grid
R/W
0: No DHW pump
1: Instant hot water
2: Disinfection
3: Circulation
4: Circulation and disinfection
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
R/W
0: No
1: Pwr consmp ctrl
R/W
0: No
1: Yes
R/W
0: No
1: Yes (DHW)
2: Yes (DHW + SH)
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
0
2
0
0
0
R/O
0~5
0: LT split
R/O
0
R/W (*1)
0: Reversible (*1)
R/O (*2)
1: Heating only (*2)
R/O
0: no heater (*7)
(*4,*5,*6)
2: 3V (*4)
R/W (*7)
3: 6V (*5)
4: 9W (*6)
R/O
0: No
1: Yes
R/O
0: No
1: Yes
1
11/12
Installer setting at variance with
default value
Date
Value
4P681207-1 - 2021.12