Daikin ERGA06EAV3H Installer's Reference Manual page 232

Hide thumbs Also See for ERGA06EAV3H:
Table of Contents

Advertisement

11
|
Configuration
Installer reference guide
232
Bizone kit system type
#
Code
[9.P.2]
[E-0C]
Additional zone pump fixed PWM
The speed of the additional zone pump can be fixed with this setting.
#
Code
[9.P.3]
[7-0A]
Main zone pump fixed PWM
The speed of the main zone pump can be fixed with this setting.
#
Code
[9.P.4]
[7-0B]
Description
Bizone system type
0 Without hydraulic separator / no
direct pump
a
1 With
hydraulic
direct pump
a
c
2 With hydraulic separator / with
direct pump
c
a
a: Indoor unit; b: Mixing station; c: Hydraulic
separator; d: Direct pump
Description
Add zone pump fixed PWM: Fixed pump
speed for additional (direct) zone.
20~95% (default: 95)
Description
Main zone pump fixed PWM: Fixed pump
speed for main (mixed) zone.
20~95% (default: 95)
ERGA04~08EAV3+V3A+V37 + EHSH/X(B)04+08P30+50EF
b
separator
/
no
b
d
b
Daikin Altherma 3 R ECH₂O
4P678716-1 – 2022.01

Advertisement

Table of Contents
loading