Daikin ERGA06EAV3H Installer's Reference Manual page 287

Hide thumbs Also See for ERGA06EAV3H:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
2.E
WD curve type
Additional zone
3.4
Setpoint mode
└─ Heating WD curve
3.5
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
3.5
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
3.5
[0-02]
High ambient temp. for LWT add zone heating WD curve.
3.5
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
└─ Cooling WD curve
3.6
[0-04]
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
3.6
[0-05]
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
3.6
[0-06]
High ambient temp. for LWT add zone cooling WD curve.
3.6
[0-07]
Low ambient temp. for LWT add zone cooling WD curve.
Additional zone
3.7
[2-0D]
Emitter type
└─ Setpoint range
3.8.1
[9-05]
Heating minimum
3.8.2
[9-06]
Heating maximum
3.8.3
[9-07]
Cooling minimum
3.8.4
[9-08]
Cooling maximum
Additional zone
3.A
[C-06]
Thermostat type
└─ Delta T
3.B.1
[1-0C]
Delta T heating
3.B.2
[1-0E]
Delta T cooling
Additional zone
3.C
WD curve type
Space heating / cooling
└─ Operation range
4.3.1
[4-02]
Space heating OFF temp
4.3.2
[F-01]
Space cooling OFF temp
Space heating / cooling
4.4
[7-02]
Number of zones
4.5
[F-0D]
Pump operation mode
4.6
[E-02]
Unit type
4.7
[9-0D]
Pump speed limitation
Space heating / cooling
4.9
[F-00]
Pump outside range
4.A
[D-03]
Increase around 0°C
4.B
[9-04]
Overshoot
4.C
[2-06]
Antifrost
Tank
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*6) *EKECBUA3V*_(*7) *EKECBUA6V*_(*8) *EKECBUA9W*_(*9) BUH less_
(*10) 04P_(*11) 08P
Range, step
Default value
R/W
0: 2-points
1: Slope-Offset
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
25°C
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0
40°C
[2-0C]=1
45°C
[2-0C]=2
55°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
5°C
[2-0C]=2
18°C
R/W
[9-07]~[9-08]°C, step: 1°C
22°C
R/W
25~43°C, step: 1°C
35°C
R/W
10~25°C, step: 1°C
20°C
R/O
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
15~37°C, step: 1°C
25°C
R/W ([2-
[2-0C]=2:
0C] ≠ 2)
37~60, step: 1°C
R/O ([2-
65°C
0C] = 2)
[2-0C]≠2:
37~55, step: 1°C
55°C
R/W
5~18°C, step: 1°C
5°C
R/W
18~22°C, step: 1°C
22°C
R/W
1: 1 contact
2: 2 contacts
[2-0D] ≠2
[2-0D] ≠2 (Radiator)
R/W
3~10°C, step: 1°C
[2-0D] =2
5°C
R/O
[2-0D] = 2 (Radiator)
10°C
R/W
3~10°C, step: 1°C
5°C
R/O
0: 2-points
1: Slope-Offset
R/W
14~35°C, step: 1°C
22°C
R/W
10~35°C, step: 1°C
20°C
R/W
0: Single zone
1: Dual zone
R/W
0: Continuous
1: Sample
2: Request
R/W (*1)
0: Reversible (*1)
R/O (*2)
1: Heating only (*2)
R/W
0~8, step:1
0 : No limitation
1~4 : 90~60% pump speed
5~8 : 90~60% pump speed during
sampling
6 80% pump speed
R/W
0: Restricted
1: Allowed
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
R/W
1~4°C, step: 1°C
2°C
R/W
0: No
1: Yes
3/12
Installer setting at variance with
default value
Date
Value
4P681207-1 - 2021.12