ERGA04~08EAV3+V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1 – 2022.01
INFORMATION
Start by purging the air out of the unit with the manual air vent valves. Only if water
escapes the valve after opening it, you can start the manual air purge function. When
almost all the air is removed, perform an automatic air purge. If necessary, repeat
performing the automatic air purge until you are sure that all air is removed from the
system. During air purge function, pump speed limitation [9‑0D] is NOT applicable.
Finally open the two manual air purging valves and check if the circuit is sufficiently
filled with water.
The air purge function automatically stops after 30 minutes.
INFORMATION
For best results, air purge each loop separately.
To purge the air out of the unit with the manual air vent valves
a
b
a, b, c Manual air vent valve
1 Connect a hose to the manual air vent valve a. Direct the free end away from
the unit.
2 Open the valve by turning until no more air escapes, then close it again.
3 Repeat step 1 and 2 for valve b.
4 In case that an option backup heater is installed, repeat step  1 and 2 for
valve c.
To perform a manual air purge
Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off
Space heating/cooling and Tank operation.
1 Set the user permission level to Installer. See
the user permission
2 Go to [A.3]: Commissioning > Air purge.
3 In the menu, set Type = Manual.
4 Select Start air purge.
5 Select OK to confirm.
Result: The air purge starts. It stops automatically when ready.
4
level" [
 147].
12
Commissioning
|
c
"To change
Installer reference guide
243