Daikin Altherma 3 R ECH2O Installation Manual

Daikin Altherma 3 R ECH2O Installation Manual

Hide thumbs Also See for Altherma 3 R ECH2O:
Table of Contents

Advertisement

Quick Links

Installation manual
Daikin Altherma 3 R ECH₂O
https://daikintechnicaldatahub.eu
EBSH11P30DF
EBSHB11P30DF
EBSH11P50DF
EBSHB11P50DF
EBSH16P30DF
EBSHB16P30DF
EBSH16P50DF
EBSHB16P50DF
EBSX11P30DF
EBSXB11P30DF
EBSX11P50DF
EBSXB11P50DF
EBSX16P30DF
EBSXB16P30DF
Installation manual
EBSX16P50DF
English
Daikin Altherma 3 R ECH₂O
EBSXB16P50DF

Advertisement

Table of Contents
loading

Summary of Contents for Daikin Altherma 3 R ECH2O

  • Page 1 Installation manual Daikin Altherma 3 R ECH₂O https://daikintechnicaldatahub.eu EBSH11P30DF EBSHB11P30DF EBSH11P50DF EBSHB11P50DF EBSH16P30DF EBSHB16P30DF EBSH16P50DF EBSHB16P50DF EBSX11P30DF EBSXB11P30DF EBSX11P50DF EBSXB11P50DF EBSX16P30DF EBSXB16P30DF Installation manual EBSX16P50DF English Daikin Altherma 3 R ECH₂O EBSXB16P50DF...
  • Page 2 3P664373-2A...
  • Page 3 3P664373-2A...
  • Page 4: Table Of Contents

    To connect the DHW output........34 ▪ Installation instructions 7 Configuration ▪ Format: Paper (in the box of the indoor unit) Overview: Configuration ............35 7.1.1 To access the most used commands ......35 Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 5: Specific Installer Safety Instructions

    WARNING Daikin website (publicly accessible). ▪ Do NOT pierce or burn refrigerant cycle parts. ▪ The full set of latest technical data is available on the Daikin ▪ Do NOT use means to accelerate the defrosting Business Portal (authentication required).
  • Page 6: About The Box

    WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation. Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 7: To Remove The Accessories From The Indoor Unit

    Otherwise the installation manual of the Backup Heater. unit may be damaged or in extreme cases catch fire. 360° ≥100 ≥500 a ≥100 a+b ≥600 b ≥300 Screw plug EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 8: Special Requirements For R32 Units

    WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. NOTICE ▪ Pipework shall be protected from physical damage.
  • Page 9: Installation Patterns

    =1.90 m + Chimney height release Installation with chimney connected to the outside. The release height is not relevant. There are no requirements to the minimum floor area. Not applicable EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 10 1× O-ring Flat gasket ▪ Socket's connection point for the chimney = 1" male thread. Use a compatible counterpart for the chimney. ▪ Make sure the connection is airtight. Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 11 ▪ Must be a permanent opening that cannot be closed. ▪ Must be ≥50% of A (minimum bottom opening area). nv-min Min. 50% ▪ Must be ≥1.5 m from the floor. of A nv-min (≥A nv-min EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 12 Ventilation openings must comply with A and with nv-min "Conditions ventilation openings" on previous page). Min. 50% Min. 50% ΔH1 of A of A nv-min nv-min (≥A (≥A nv-min nv-min Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 13 Floor area (m²) 5.00 10.00 15.00 20.00 25.00 3.30 2.10 3.47 2.21 3.91 2.49 2.03 4.34 2.77 2.26 1.96 4.78 3.04 2.49 2.15 1.93 5.04 3.21 2.62 2.27 2.03 EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 14 6.038 4.488 2.835 1.146 2.00 7.750 5.470 3.806 2.053 0.274 2.20 6.902 4.354 2.461 0.508 2.40 6.143 3.343 1.237 2.60 5.454 2.419 0.115 2.80 4.825 1.568 3.00 4.245 0.776 Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 15: Opening And Closing The Unit

    Example: If the refrigerant charge is 4.3 kg, use the row of 4.4 kg. Total refrigerant charge (kg) (dm²) nv-min 10.1 10.4 10.6 10.9 11.1 11.3 11.5 11.8 EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 16: To Lower The Switch Box Of The Indoor Unit And Remove The Top Cover

    You must connect the drain hoses to an appropriate drain according to the applicable legislation. 1 Open the screw plug. 1× Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 17: Piping Installation

    ▪ with a heat resistance of at least 120°C ▪ Insulation thickness Pipe outer diameter Insulation inner Insulation thickness (Ø diameter (Ø 9.5 mm (3/8") 12~15 mm ≥13 mm 15.9 mm (5/8") 17~20 mm ≥13 mm Ø Ø Ø Ø EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 18: Connecting Refrigerant Piping

    ▪ Water temperature. All installed piping and piping accessories See the recommended procedure as described in "8.2  Checklist commissioning" [ 4  44]. (valve, connections,…) MUST withstand following during temperatures: Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 19: Connecting Water Piping

    Do NOT exceed the maximum tightening torque (Thread size 1", 25-30  N•m). To avoid damage, apply the necessary countertorque with a suitable tool. ≤Ø7 mm EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 20: To Connect A Pressure Vessel

    1 m water column = 0.1 bar). Make sure that the pressure relief valve does not open. 6 Close the manual air vent valves as soon as water emerges free of bubbles. Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 21: To Protect The Water Circuit Against Freezing

    1 Open the shut-off valve for the cold water supply. 2 Open all hot water taps in the system to make sure that the tapped water flow is as high as possible. EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 22: To Insulate The Water Piping

    "6.3.12 To connect the safety least 20  mm to prevent condensation on the surface of the thermostat (normally closed insulation. contact)" [ 4  31]. Smart Grid "6.3.13 To connect a Smart Grid" [ 4  32]. Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 23: To Connect The Electrical Wiring To The Indoor Unit

    Wires: 2×0.75 mm² account adequately. The cable routing in normal position is longer than in service position. [9.B.1]=2 (External sensor = Room) [1.7] Room sensor offset EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 24: To Connect The Main Power Supply

    2 Connect the main power supply. In case of normal kWh rate power supply Interconnection Wires: (3+GND)×1.5 mm² cable Power supply Wires: 1N+GND indoor unit Maximum running current: 6.3 A — Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 25: To Connect The Backup Heater Power Supply

    MUST be protected by the safety devices required by the applicable legislation. CAUTION To guarantee the unit is completely earthed, ALWAYS connect the backup heater power supply and the earth cable. EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 26 Connect the backup heater power supply as follows: 1N~, 50 Hz 230 V AC Model (power Connections to backup heater power supply) supply *3V (3V: 1N~ 230 V) SWB2 Q1DI 1N~, 50 Hz 230 V AC Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 27: To Connect The Backup Heater To The Main Unit

    2 Switch box 3 Switch box cover 4 Top cover 2 Connect both connection cables from the backup heater EKECBU* to the appropriate connectors as shown in the illustration below. EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 28: To Connect The Electricity Meters

    3 Switch box cover terminals as shown in the illustration below. 4 Top cover 2 Connect the electricity meters cable to the appropriate terminals as shown in the illustration below. Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 29: To Connect The Alarm Output

    2 Connect the alarm output cable to the appropriate terminals as 4 Top cover shown in the illustration below. 2 Connect the space cooling/heating ON/OFF output cable to the appropriate terminals as shown in the illustration below. EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 30: To Connect The Changeover To External Heat Source

    4 Top cover 2 Install the switch box metal insert. 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 31: To Connect The Safety Thermostat (Normally Closed Contact)

    8H-03 will occur. Safety thermostat contact: 16 V DC detection (voltage supplied by PCB). The voltage-free contact shall ensure the minimum applicable load of 15 V DC, 10 mA. EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 32: To Connect A Smart Grid

    Jumper (factory-mounted). If you also connect a safety thermostat (Q4L), replace the jumper with the safety thermostat wires. Smart Grid pulse meter 1 Install the switch box metal insert. Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 33 3 Install the components of the Smart Grid relay kit as follows: 9 10 X 5M.10 X 5M.9 X 5M 2× 2× 5 Connect the high voltage wiring as follows: EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 34: To Connect The Wlan Cartridge

    4 Top cover 2 Connect the DHW signal cable as shown in the illustration below. 6.3.15 To connect the solar input Wires: 0.5 mm² Solar input contact: 5 V DC (voltage supplied by PCB) Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 35: Configuration

    (via the unit), the configuration wizard starts to help you configure the system. The Advanced user pin code is 1234. Additional menu items for the user are now visible. EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 36: Configuration Wizard

    When confirmed, the system will restart and recent changes will be applied. Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 37 NOTICE An overpressure bypass valve can be integrated in the system. Keep in mind that this valve might not be shown on the illustrations. EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 38: Configuration Wizard: Backup Heater

    If the storage temperature setpoint is higher than 50°C and 0: Underfloor Maximum 55°C Variable no auxiliary boiler is installed, Daikin recommends NOT to heating disable the backup heater second step because it will have 1: Fancoil unit Maximum 55°C...
  • Page 39: Configuration Wizard: Additional Zone

    Influence of the LWT setpoint mode [2.4] is as follows: ▪ In Fixed LWT setpoint mode, the scheduled actions consist of desired leaving water temperatures, either preset or custom. EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 40: Weather-Dependent Curve

    See curves" [ 4  41]. "7.3.4 Using weather-dependent 7.3.2 2-points curve Define the weather-dependent curve with these two setpoints: ▪ Setpoint (X1, Y2) ▪ Setpoint (X2, Y1) Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 41: Using Weather-Dependent Curves

    Confirm changes and return to the submenu. temperatures … temperatures … Cold ↑ — 7.3.4 Using weather-dependent curves ↓ — Configure weather-dependent curves as following: Cold ↓ ↑ Cold Cold — ↑ EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 42: Settings Menu

    ON/OFF condition. 7.4.2 Additional zone Thermostat type Only applicable in external room thermostat control. For more info zone" [ 4  42]. about the functionality, see "7.4.1 Main Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 43: Menu Structure: Overview Installer Settings

    Add zone pump fixed PWM Main zone pump fixed PWM Mixing valve turning time Only applicable in Swedish language. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 44: Commissioning

    The power supply voltage matches the voltage on the commissioning checklist is also available on the Daikin identification label of the unit. Business Portal (authentication required). There are NO loose connections or damaged electrical The general commissioning checklist is complementary to components in the switch box.
  • Page 45: To Perform An Air Purge

    1 Set the user permission level to Installer. See "To — level" [ 4  35]. change the user permission 2 Go to [A.2]: Commissioning > Actuator test run. EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 46: Hand-Over To The User

    ▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 47: 10 Technical Data

    10 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 10.1 Piping diagram: Indoor unit...
  • Page 48: Wiring Diagram: Indoor Unit

    (1) Main power connection (1) Main power connection SWB1 Main switch box Outdoor unit Outdoor unit SWB2 Backup heater switch box SWB1 Switch box (2) User interface (2) User interface Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 49 Smart Grid contacts Smartgrid feed-in Smart Grid feed-in Solar input Solar input Space C/H On/OFF output Space cooling/heating On/OFF output SWB1 Switch box (4) Option PCBs (4) Option PCBs EBSH/X(B)11+16P30+50DF Installation manual Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 50 2 core Power limitation demand input 4 Only for remote user interface 2 core A8P: X801M: 4-5 signal 2×0.75 X 5M: 11-12 A14P: P1-P2 user interface communication 4D135453 Installation manual EBSH/X(B)11+16P30+50DF Daikin Altherma 3 R ECH₂O 4P663483-1A – 2021.11...
  • Page 52 4P663483-1 A 00000000 4P663483-1A 2021.11 Verantwortung für Energie und Umwelt...