Daikin Vision Installation And Maintenance Manual page 26

Table of Contents

Advertisement

Figure 41: Wheel-to-Inlet Funnel Relationship—18 to 36
Belt-Drive Plenum Fans
Cross Section Reference
B
FROM FUNNEL END TO
FANWHEEL OPENING END
A
C
Table 7: Wheel-to-Inlet Funnel Relationship—18 to 36
Belt-Drive Plenum Fan
Wheel-Funnel Parameters
Size
A
18
0.38
20
0.42
22
0.45
24
0.51
27
0.55
30
0.62
33
0.55
36
0.63
IM 915-13 • VISION - EXTENDED SIZES
EQUALLY SPACED
AROUND DIAMETER
B
C
0.86
3.88
1.11
3.88
1.11
3.88
1.11
3.88
1.36
4.5
1.36
4.5
1.5
5.0
1.5
5.0
Figure 42: Wheel-to-Inlet Funnel Relationship—40 to 60
Belt-Drive Plenum Fans
Cross Section Reference
FUNNEL END TO FAN
C
Table 8: Wheel-to-Inlet Funnel Relationship—40 to 60
Belt-Drive Plenum Fan
Wheel-Funnel Parameters
Size
A
40
0.82
44
0.91
49
1.00
54
1.10
60
1.23
26
Operation Guidelines
A
WHEEL OPENING
EQUALLY
SPACED AROUND
B
DIAMETER
B
2.00
2.25
2.50
2.50
3.00
www.DaikinApplied.com
C
4.88
5.50
5.50
5.50
5.50