Table 15: DDPL Factors for Free and Ducted Inlet –
Non-Standard Density Method, Daikin Applied Piezo Ring
DDPL Size
C1 Free Inlet
12
15
16
18
20
22
24
27
30
33
36
40
44
Table 16: DDPL Factors for Free and Ducted Inlet –
Standard Density Method, Daikin Applied Piezo Ring
DDPL Size
Free Inlet F
12
1004.66
15
1261.99
16
1526.96
18
1675.69
20
2117.33
22
2710.75
24
3312.67
27
3901.60
30
5017.64
33
5942.72
36
7274.52
40
9179.91
44
10891.71
IM 915-13 • VISION - EXTENDED SIZES
C1 Ducted Inlet
783.66
792.43
767.48
763.62
732.77
757.40
612.29
619.65
653.83
652.65
674.42
673.16
679.53
681.34
656.57
660.15
691.07
692.12
675.26
677.89
675.83
676.67
699.51
694.22
681.07
681.01
Ducted
Wheel
Area A
Inlet F
Diameter
1016.46
0.344
12.40
1260.20
0.439
14.00
1572.35
0.552
15.75
1672.77
0.721
18.25
2110.61
0.865
20.00
2693.35
1.074
22.25
3319.41
1.300
24.50
3929.94
1.582
27.00
5033.71
1.957
30.00
5979.46
2.362
33.00
7316.07
2.885
36.50
9089.14
3.513
40.25
10880.24
4.285
44.50
Optional Transducer for Piezometer Rings
A transducer is available for Piezometer rings. Factory
mounting locations for the fan transducer is shown in
for direct-drive plenum fans.
for fan array. Wiring for the transducer is field-supplied and
installed.
30
Daikin Applied Fan Array
Figure 47
Figure 48
shows the installation
www.DaikinApplied.com