Standard Operating Temperature; Expanded Operating Temperature - Dell EMC PowerEdge MX7000 Field Service Manual

Hide thumbs Also See for EMC PowerEdge MX7000:
Table of Contents

Advertisement

Table 42. Maximum shock pulse specifications (continued)
Maximum shock pulse
Storage
Table 43. Maximum altitude specifications 
Maximum altitude
Operating
Storage
Table 44. Operating temperature derating specification 
Operating temperature
derating
Up to 35°C (95°F)
35°C to 40°C (95°F to
104°F)
40°C to 45°C (104°F to
113°F)

Standard operating temperature

Table 45. Standard operating temperature specifications 
Standard operating temperature
Continuous operation
(For altitude less than 950 m or 3117 ft)

Expanded operating temperature

Table 46. Expanded operating temperature specifications 
Expanded operating
temperature
Continuous operation
≤ 1% of annual operating
hours
NOTE:
When operating in the expanded temperature range, the performance of the system may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD
panel and in the System Event Log.
80
Technical specifications
Specifications
Shock pulses in the positive z axis of 71 G for up to 2 ms.
Shock pulses in the positive and negative x and y axis of 20 G for up to 7 ms.
Specifications
3048 m (10,000 ft)
12,000 m (39,370 ft)
Specifications
Maximum temperature reduces by 1°C/300 m (1°F/547 ft), above 950 m (3,117 ft).
Maximum temperature reduces by 1°C/175 m (1°F/319 ft), above 950 m (3,117 ft).
Maximum temperature reduces by 1°C/125 m (1°F/228 ft), above 950 m (3,117 ft).
Specifications
5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to 35°C), the system can operate
continuously in temperatures as low as 5°C and as high as 40°C.
For temperatures 35°C to 40°C, derate maximum allowable temperature by 1°C per 175 m (1°F
per 319 ft) above 950 m (3,1171 ft).
–5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C–35°C), the system can operate
down to –5°C or up to 45°C for a maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, derate maximum allowable temperature by 1°C per 125
m (1°F per 228 ft) above 950 m (3.117 ft).
Specifications
10°C to 35°C (50°F to 95°F)
with no direct sunlight on the equipment.