User Setup
Dry Contact Operation
Dry Contact Polarity (Setup Step 25)
Open (Normally Open) - The dry contact is open
until the connected device closes the circuit.
'Idle'
'Active'
'Idle'
'Active'
Closed (Normally Closed) - The dry contact is
closed until the connected device opens the circuit.
'Idle'
'Active'
Dry Contact Use (Setup Step 26)
Condensate Pan – If selected and the dry
contact is active, "CONDENSATE PAN"
appears on the display and cooling is turned
off to try to halt condensate production. If the
condition clears, cooling is allowed to resume
but "CONDENSATE PAN" will continue to be displayed until any button is
pushed. This is meant to inform you that an overflow had occurred. Note
that if you are using the internal condensate sensor from your Climate
Master heatpump, select FDD instead of Condensate Pan.
Vacation – If selected and the dry contact is active, "AWAY" appears on
the display and the thermostat is forced into AWAY settings. These
settings can only be altered via the Skyport website
(continued next page)