User Setup
Deadband Settings (Setup Steps 15-18)
The Deadband is the number of degrees or
minutes that the thermostat waits before it
initiates the stages of heating or cooling.
1st Stage Deadband (Setup Step 15)
Specifies the temperature difference between
the room temperature and the desired setpoint
before the first stage of heating or cooling
is allowed to turn on. (1 - 6 degrees) For
example, if the heat setpoint is 68˚ and the 1st
Stage deadband is set to 2 degrees, the room
temperature will need to reach 66˚ before the
heat turns on.
2nd Stage Deadband (Setup Step 16)
Specifies the additional temperature difference
after the first stage turns on before the second
stage is activated. (0˚ - 10˚)
Minutes Between 1st and 2nd Stage
(Setup Step 17)
Specifies the minimum time (in minutes) after the
first stage turns on before the second stage can
turn on. (0 - 60)
2nd Stage Turnoff Point (Setup Step 18)
Specifies whether second stage will turn off at
first stage deadband or remain on until the room
temperature demand is satisfied. Choose
between Deadband or Setpoint.