Appendix A: Power Vent Locations - Montigo Divine H36PV Installation & Maintenance Manual

Table of Contents

Advertisement

Appendix A: Power Vent Locations

Horizontal
Detail
A = clearance to the termination frame above grade, veranda, porch, deck,
or balcony [30 inches (75 cm) minimum]
B = clearance to door, or sides and top of window, that may be opened [30
inches (75 cm) minimum for appliances.
C = clearance to bottom of window that may be opened horizontally [36
inches (92 cm) minimum for appliances.
D = no clearance to permanently closed window when installed with approved
glass penetration termination
E = clearance to permanently closed window [30 inches 75 cm recommended
to prevent condensation on window]
F = vertical clearance to ventilated soffit located above the termination
within a horizontal distance of [30 inches 75 cm] from the centreline of
the termination [30 inches (75 cm) minimum]
G = c l e a r a n c e
t o
u n v e n t i l a t e d
( 7 5
c m )
m i n i m u m
[30 inches (75 cm) minimum to combustibles]
H = clearance to outside corner [30 inches (75 cm) minimum]
I =
clearance to inside corner [30 inches (75 cm) minimum]
J = * not to be installed above a meter/regulator assembly within
40" (103 cm) horizontally from the centreline of the regulator
K = clearance to service regulator vent outlet [3 feet minimum in the United
States] [*6 feet (1.8 m) minimum in Canada]
L = clearance to non-mechanical air supply inlet to building or the combustion
air inlet to any other appliance [16 inches (41 cm) minimum for appliances
≤100 000 BTU/H (30kW)]
M = clearance to mechanical air supply inlet [*6 feet (1.8 m) minimum]
XG0649 - 080921
Appendix
Appendix
s o f f i t
[ 3 0
i n c h e s
t o
n o n - c o m b u s t i b l e s ]
H36PVN Power Vent Indoor Gas Fireplace
V
Vertical Detail
N =
clearance above paved sidewalk or a paved driveway located on public
property [*7 feet (2.1 m) minimum]
P = clearance under veranda, porch, deck, or balcony [30 inches (75
cm) minimum
to non-combustibles] [30 inches (75 cm) minimum
combustibles]
Q = clearance above a roof [18 inches (46 cm) minimum]
R = clearance to adjacent walls and neighboring buildings [30 inches (75
cm) minimum]
S = clearance from corner in recessed location [30 inches (75 cm) minimum]
T = maximum depth in recessed location [48 inches (122 cm) minimum]
U = minimum width for back wall of recessed location [60 inches (150 cm)
minimum]
V = minimum horizontal clearance between the frames of two terminations
that are level, (see applicable Detail).
W = horizontal clearance between the frames of two terminations that are
not level. [30 inches (75 cm) minimum]
a vent shall not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both
dwellings
only permitted if veranda, porch, deck, or balcony has an open side that
is equal to or greater than the depth of the enclosed area
*
as specified in CGA B149 Installation Codes. Note: local Codes or
Regulations may require different clearance.