9.1.3 Specifications of standard wiring components
9.2 To connect the electrical wiring to the outdoor unit
RXQ-A_ARXQ-A
R32 split series
4P513661-11P – 2021.11
Tightening torques
Item
M4 (X1M)
M4 (earth)
▪
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
Component
Power supply cable
Interconnection cable (indoor↔outdoor)
Recommended circuit breaker
Residual current device
1 Remove the service cover. See
2 Strip insulation (20 mm) from the wires.
a
a Strip wire end to this point
b An excessive strip length may cause electrical shock or leakage
3 Open the wire clamp.
4 Connect the interconnection cable and power supply as follows:
1-3
Voltage
Phase
Frequency
Wire sizes
"6.2.2 To open the outdoor
b
9
Electrical installation
|
Tightening torque (N•m)
1.5~1.6
1.4~1.5
220~240 V
1~
50 Hz
3-core cable
2(a)(b)
2.5 mm
/ 4.0 mm
(a)
H05RN-F (60245 IEC 57)
(b)
H07RN-F (60245 IEC 66)
4-core cable
2
2
1.5 mm
~2.5 mm
applicable for 220~240 V
H05RN-F (60245 IEC 57)
16 A
MUST comply with applicable
legislation
unit" [
4
28].
Installer reference guide
2(b)
and
49