11
|
Commissioning

11.6 Starting up the outdoor unit

Installer reference guide
54
Prerequisite: Test run may be performed in cooling or heating mode.
Prerequisite: Test run should be performed in accordance with the operation
manual of the indoor unit to make sure that all functions and parts are working
properly.
1 In cooling mode, select the lowest programmable temperature. In heating
mode, select the highest programmable temperature. Test run can be
disabled if necessary.
2 When the test run is finished, set the temperature to a normal level. In cooling
mode: 26~28°C, in heating mode: 20~24°C.
3 The system stops operating 3 minutes after the unit is turned OFF.
INFORMATION
Even if the unit is turned OFF, it consumes electricity.
When the power turns back on after a power break, the previously selected
mode will be resumed.
See the indoor unit installation manual for configuration and commissioning of the
system.
RXQ-A_ARXQ-A
R32 split series
4P513661-11P – 2021.11