Connections And Terminal Designation - Siemens SITOP SEL1200 8 x 5 A Equipment Manual

Table of Contents

Advertisement

2.2

Connections and terminal designation

The input terminals
"0 V" connection
used to connect to the loads to be supplied (see also Chapter Installation (Page 47)).
The operating state of the device can be processed using the group signal contact
the function and content rating, see Figure 2-4 Status displays and signaling (Page 16)).
The remote reset (RST) input
down (function, see Chapter Status displays and signaling (Page 16)).
Connections and terminal designations
signed (NF); remote reset (RST)
*1)
*2)
Figure 2-2
The terminal location must first be opened for smaller conductor cross-sections and for
flexible conductors without conductor end sleeves. To do this, an appropriate slotted
screwdriver must be inserted into the square slot at the appropriate connection.
We recommend the CRIMPFOX 6 - 1212034 crimping tool to crimp conductor end sleeves. If
the conductor end sleeve is longer than the permissible length of the crimping tool, then the
end sleeve must be crimped in several steps.
Applying pulling and lateral forces to the terminal should be avoided.
SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76
can be used to establish the connection to the supply voltage. The
is used to supply the internal electronics. The output terminals
24 V DC input
0 V connection for the internal supply
24 V DC output: 1 - 4 (1 - 8)
Group signaling contact (13, 14); not as-
Do not subject the end stop to higher loads
8 mm of insulation has to be stripped when using conductor end sleeves
Terminal data
Description, device design, dimension drawing
2.2 Connections and terminal designation
is used to reset outputs that have automatically been shut
2 spring-loaded terminals
2 spring-loaded terminals
one spring-loaded terminal each
one spring-loaded terminal each
are
(for
13