Page 3
Danger in case of none designated use of the product! Serious injury may result. Siemens products may only be used for the applications indicated in the cata- log and in the relevant technical description. If third-party products and com- ponents are used, these must be recommended or approved by Siemens. To...
Page 4
Tolerances of the prescribed tightening torques Note: If not indicated differently, the tolerances of the prescribed tightening torques in these operating instructions are ±10 %. SIPLUS PSU Power Supply Unit A5E00854207E 4 of 30 Copyright (C) Siemens AG 2018 V 8.00 released...
Replace of an Equipment ..................... 27 Order Designations ........................ 29 Annex ............................30 10.1 List of Figures ........................30 10.2 List of Tables ........................30 SIPLUS PSU Power Supply Unit A5E00854207E 5 of 30 Copyright (C) Siemens AG 2018 V 8.00 released...
Programmable Logic Controller Power Supply Unit SELV Safety Extra Low Voltage according to EN 60950-1 SIPLUS Siemens brand SPPA Siemens Power Plant Automation SIPLUS PSU Power Supply Unit A5E00854207E 6 of 30 Copyright (C) Siemens AG 2018 V 8.00 released 2018-05-03...
2 Application 2.1 Utilization SIPLUS PSU is a power supply module in electronic cabinets for the feeding and sub-distribution of the power supply DC 24 V. It was developed especially for use in instrumentation and control cabi- nets of the Siemens power station instrumentation and control systems SPPA-T2000 and SPPA- T3000 and the Siemens automation system PCS7.
SIPLUS PSU (6DL3500-8BA) 3 Design 3.1 Mechanical Structure Figure 2: Physical dimensions of the SIPLUS PSU SIPLUS PSU Power Supply Unit A5E00854207E 8 of 30 Copyright (C) Siemens AG 2018 V 8.00 released 2018-05-03...
2 x M, L1, L2 (X105 –X108) for wire cross-sections of 4 up to max. 16 mm resp. AWG 12 - 4 are disposable at every SIPLUS PSU. The feeder terminals and the branch terminals for the adjacent cabinet are internally linked.
An activating of the electronic supervision is signaled by the channel LED with a red continuous light. In addition at the signaling outputs MELD (active HIGH) and MELD_N (active LOW) a collective sta- tus signal is output. SIPLUS PSU Power Supply Unit A5E00854207E 11 of 30 Copyright (C) Siemens AG 2018 V 8.00 released...
DC output. The second output requires a pull resistor of 39 kΩ. The pull resistor is the parallel con- nection of 39 kΩ and 100 kΩ and results in 28 kΩ. or with current drawing digital DC inputs (MELD) and current sourcing digital DC inputs (MELD_N) respectively SIPLUS PSU Power Supply Unit A5E00854207E 12 of 30 Copyright (C) Siemens AG 2018 V 8.00 released...
OFF/ON OK/blown High impedance High Table 1: Signaling scheme The operating state "FAULT" is described in detail in the chapter 8.2 “Malfunctions”. SIPLUS PSU Power Supply Unit A5E00854207E 13 of 30 Copyright (C) Siemens AG 2018 V 8.00 released 2018-05-03...
SIPLUS PSU internally. The connection between M potential and cabinet earth is established by mounting the PSU at the cabinet rack. For use of the SIPLUS PSU in plants with central earthing point the internal connection between M potential and unit casing can be disconnected.
When using cabinets it is recommended to install the SIPLUS PSU in the lowermost tier. The maximum ambi- ent temperature in dependency of the consant current through the feeder diodes is to be considered according to derating in chapter 6.1.
External supply voltage is to be generated as potential free Protective Extra Low Voltage PELV (according to EN 50178). Typical value for project planning when supplying four FUM sub racks with 7.5 A current consumption each SIPLUS PSU Power Supply Unit A5E00854207E 16 of 30 Copyright (C) Siemens AG 2018 V 8.00 released...
5.3. For selection of the correct fuses see chap- ter 9 “Order Designations”. For selectivity when connecting a FUM-Sub rack EU 902 / EU903 / EU905 or a S7-400H Sub rack SIPLUS PSU Power Supply Unit A5E00854207E 17 of 30 Copyright (C) Siemens AG 2018 V 8.00 released...
As an option an external pullup can be connected to the MELD_N output in order to generate H- levels when feeding voltage driven inputs (see fig. 10). The application impedance and the MELD_N leakage current have to be considered here among other constraints. SIPLUS PSU Power Supply Unit A5E00854207E 18 of 30 Copyright (C) Siemens AG 2018 V 8.00 released...
6.1 Mounting position, heat dissipation and derating According to figure 11 the SIPLUS PSU has to be installed so that a vertical unimpeded flow of the cooling air at the heat sink on the back side of the equipment is ensured.
SIPLUS PSU (6DL3500-8BA) 6.2 Installation into the cabinet When operating the SIPLUS PSU in I & C cabinets the installation in the lowermost tier is recom- mended. The supply cables and transfer cables to the neighboring cabinet are connected vertically from below.
For the horizontal mounting position choose the position with the longest distance to the rear assembly wall in order to get an optimum heat dissipation via airflow at the heat sink. For unearthed mounting please notice chapter 7.3 “Unearthed Mounting” SIPLUS PSU Power Supply Unit A5E00854207E 21 of 30 Copyright (C) Siemens AG 2018 V 8.00 released...
Page 22
When changing the equipment, please notice chapter 8.5 “Replace of an Equipment” Step 3: For an optimal cable routing install the SIPLUS PSU in the undermost level. Screw the mounting brackets together with the underground. Tighten the screws with a torque ac- cording to chapter 5.1 “Mechanics”...
7.3 Unearthed Mounting For a mounting isolated from earth (e.g. in plants with a central earthing point) the SIPLUS PSU of- fers the possibility to undo the connection of the reference potential of the DC 24 V supply voltage to the cabinet earth.
High unit replace- ment Table 2: Fault diagnosis Other possible conditions of the LED displays are described in chapter 4.7 “Signaling Scheme” SIPLUS PSU Power Supply Unit A5E00854207E 24 of 30 Copyright (C) Siemens AG 2018 V 8.00 released 2018-05-03...
24 V supply voltage. At the auxiliary supply unit an output voltage of 30 V and a current limitation of 60 A must be adjustable. Repair of faulty feeding diodes is not provided. In that case the SIPLUS PSU must be replaced by a new unit (see chapter 8.5 “Replace of an Equipment”).
Page 26
Connect the supply cable to L2 again. Note: The supply cable at L1 must be connected during the whole test step for the supply of the neighbor cabinet! SIPLUS PSU Power Supply Unit A5E00854207E 26 of 30 Copyright (C) Siemens AG 2018 V 8.00 released...
Turn the auxiliary power supply unit off and disconnect it from L1/L2 and M. Connect the feeding ca- ble to M again. 8.4 Repair Repairs of the SIPLUS PSU are not provided. A defective SIPLUS PSU must be replaced by a new unit (see subsequent chapter) 8.5 Replace of an Equipment...
Page 28
Step 6: Load assumption by U1 and U2 U3 has to be deactivated so that SIPLUS PSU 1 as well as 2 are supplied by the voltage sources U1 and U2. U3 can be removed afterwards. The replace of the equipment is completed.
Schottky-type Plug set for SIPLUS PSU (21 pieces/set) 6DL9904-8AA (not included in the scope of delivery of the SIPLUS PSU) Fuse set blade fuses 15 A 6DL9905-8AA for SIPLUS PSU (20 pieces/set) Fuse set blade fuses 8 A...