Sel1200 8 X 10 A 6Ep4438-7Fb00-3Dx0 - Siemens SITOP SEL1200 8 x 5 A Equipment Manual

Table of Contents

Advertisement

Mounting position, mounting clearances
4.2 Other mounting positions
4.2.3

SEL1200 8 x 10 A 6EP4438-7FB00-3DX0

NOTICE
In total, the maximum device load must not exceed 60 A. The derating of 2 %/K must also
be complied with here. At 70 °C, this corresponds to a total maximum device load of 48 A.
Figure 4-18
Figure 4-19
Figure 4-20
38
Mounting position 1
Mounting position 2
Mounting position 3
SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76

Advertisement

Table of Contents
loading

Table of Contents