After proper damper operation has been verified, the installer can now check and verify that
each Remote Room Sensor corresponds to the proper zone damper in the same zone. For
systems with remote room sensor, temporarily disconnect any other zone Remote Room Sensor
(at sensor location). That zone damper will now open, while the Zone 1 damper will close.
For systems using Smart Sensors (when available), the installer may press and hold the Hold
and Mode buttons simultaneously for 3 seconds to change the zone under test. This should be
done with each zone to verify that the zone sensor corresponds to that particular zone.
Once each zone has been checked, touch DONE to return to the ZONING CHECKOUT
menu.
6.4.8.3. Zone Duct Assessment
This screen shows the results from the previous duct assessment. The duct assessment is
performed at initial start-up and at 1 P.M. or the installer selected time each day. If another duct
assessment is desired, the service technician should perform a re-install of the system.
NOTE: A Duct Assessment will automatically occur every 24 hours at selected time to check
system static and calibrate dampers.
Once the duct assessment is complete, touch DONE to return to the ZONING CHECKOUT
menu.
6.4.8.4. Sensor Type
This option shows a list of all zones with corresponding sensor types.
6.5. Service Information
The Service Info menu will only show the equipment installed in the system. To enter this menu
of options, touch SERVICE INFORMATION.