The system will then close all zones and take a pressure measurement, getting a value for the
duct leakage up to and through the dampers. With these static pressure measurements, the
system will calculate the relative size of each zone as well as the percent leakage through the
dampers at the end of the process, the display will show the relative size of each zone duct.
If the Ion System Control detects an error (damper not moving or damper wired backwards), it
will perform the duct assessment again. If it still detects a damper problem, it will default the
measurements into equal sizes, with 10% leakage, and display the zone number for the
suspected zone damper.
NOTE: The daily duct assessment will occur even if static pressure monitoring is disabled. This
is done to ensure that the system will continue to provide proper airflow for all installed
equipment, since duct system changes may occur at any time, such as opened or closed
registers.
After the duct assessment is complete, touch NEXT.
6. Service Menu
The Service menus contain a set of vital information. This information enables the installer or
service person to view a summary of what has been installed, etc. This information is not
covered in the Owner's Manual.
To enter service menus, touch menu, then touch and hold the SERVICE icon, for at least ten
seconds, until the icon turns green. The following screens are available in installation and
service. To return to the previous screen, touch BACK. To exit the Service menus, touch
DONE.
NOTE: See the Owner's Manual for information regarding software upgrades.
NOTE: The user "selection of temperature units" affects the user screens only. The service
screens use degree F only. The user "selection of temperature units" is under the display icon on
the main menu.