6.4. Check out
PROPERTY DAMAGE AND/OR PERSONAL INJURY HAZARD
Failure to follow this warning could result in property damage, personal injury or death.
Before running Check Out mode, make sure that all HVAC equipment is properly installed.
See the equipment installation instructions for details and additional safety information.
See the Ion System Control Product Data for compatible units and more information. Touch
CHECKOUT to view the equipment installed in the system. Perform checkout test to make
sure each piece of equipment is operating properly.
6.4.1. Electric Heat
If you have a fan coil with electric heaters, this menu item will allow the heaters to be exercised.
With self-identifying electric heaters, three stages of electric heat are available to be exercised
in any combination. Non-identifying heaters will only provide one stage of heat; or perhaps may
have fixed-timed staging. See the instructions provided with the electric heat accessory. After
the selections are made, touch START.
• Low Heat: Selectable from 0 to 120 minutes. Default = 5 minutes
• Medium Heat: Selectable from 0 to 120 minutes. Default = 5 minutes
• High Heat: Selectable from 0 to 120 minutes. Default = 5 minutes
6.4.2. Furnace
Make sure the furnace is properly installed.
This option allows the furnace to be exercised. First, a low heat run time and high heat run time
are selected. The furnace will execute its ignition start-up sequence. This sequence will be
displayed on the screen. After the gas valve and blower motor turn on, the screen will show the
current operating status of the furnace. After the selections are made, touch START.
• Low Heat: Selectable from 0 to 120 minutes. Default = 5 minutes