DIP switch setting list (Outdoor unit)
Models FDC100, 125, 140VNX, 100, 125, 140VSX
(1) Control PCB
Models FDC100,125,140VNX,100,125,140VSX
Switches
Pump down operation
SW1
JSW1-1
JSW1-2
Model selection
JSW1-3
JSW1-4
Defrost condition
SW3-1
Snow protection control
SW3-2
SW3-3
Test run SW
Test run mode
SW3-4
Model selection
SW4-1
SW4-2
Model selection
Reserved
SW4-3
SW4-4
Reserved
Reserved
SW5-1
Reserved
SW5-2
SW5-3
Reserved
Reserved
SW5-4
Table 1: Outdoor unit model selection with JSW1-1-JSW1-4 and SW4-1-SW4-2
Switches
FDC100VNX FDC100VSX FDC125VNX FDC125VSX FDC140VNX FDC140VSX
JSW1-1
OFF
JSW1-2
OFF
JSW1-3
OFF
JSW1-4
OFF
SW4-1
ON
SW4-2*
ON
(2) Inverter PCB
FDC100, 125, 140VNX FDC100, 125, 140VSX
Switches
Single phase models
JSW10-1
OFF
JSW10-2
OFF
JSW10-3
OFF
JSW10-4
OFF
JSW11-1
OFF
JSW11-2
OFF
JSW11-3
ON
JSW11-4
ON
* When checking inverter PCB of FDC100 - 140 models with inverter checker, turn JSW10-4 ON.
(Regarding the checking method of inverter PCB with inverter checker, refer to page 103 for details)
Description
Normal*/Pump down
Normal*/Cold region
Normal*/Snow protection
Normal*/Test run
Cooling*/Heating
Domestic/Overseas*
3-phase/Single phase
* Default setting
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
3-phase models
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
Default setting
OFF
As per model
OFF
OFF
OFF
OFF
ON
As per model
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
* 3-phase: OFF/Single phase: ON
98
-
-
'17 • PAC-T-257
Remarks
Normal
See table 1
Normal
Normal
Normal
Cooling
Overseas
See table 1
See table 1
Keep OFF
Keep ON
Keep OFF
Keep OFF
Keep OFF
Keep OFF