Error code
Indoor display
Remote control:
E49
Outdoor unit
Outdoor unit
inverter PCB
1. Applicable model
All models
2. Error detection method
3. Condition of error displayed
4. Presumable cause
Note:
RUN light
Green LED
Keeps flashing
control PCB
Yellow LED
Keeps flashing
5. Troubleshooting
From previous page.
service valve fully
connections of low
pressure sensor and suction pipe
temprerature thermistor
low pressure sensor, suction
pressure normal during
TIMER light
Content
Red LED
1-time flash
low pressure sensor anomaly (2/2)
Diagnosis
Is the
opened?
YES
Are the
connector OK?
YES
Are the
characteristics of
pipe temperature
thermistor OK?
YES
Is the low
operation?
YES
145
-
-
'17 • PAC-T-257
Low pressure error or
Countermeasure
Open fully.
NO
Correct.
NO
Defective low pressure
NO
sensor, suction pipe
temperature thermistor ➞
Replace.
Charge refrigerant.
NO
Defective outdoor unit
control PCB ➞ Replace.
(Defective low pressure
sensor, suction pipe
temperature thermistor
circuits)