Preset point of the protective devices
Parts name
Temperature sensor
(for protection
overloading in heating)
Temperature sensor
(for frost prevention)
Temperature sensor
(for protection high
pressure in cooling.)
Temperature sensor
(for detecting discharge
pipe temp.)
High pressure switch
(for protection)
Low pressure sensor
(for protection)
Equipped
Mark
unit
Th1
Indoor unit
Th2
1
Outdoor unit
Tho-R
Outdoor unit
Tho-D
63H1
Outdoor unit
Outdoor unit
LPT
100, 125, 140 model
OFF 16℃
ON 17℃
OFF 8℃
ON 2.5℃
OFF 51℃
ON 65℃
OFF 115℃
ON 85℃
OFF 4.15MPa
ON 3.15MPa
OFF 0.227MPa
ON 0.079MPa
21
-
-
'17 • PAC-T-257