Mitsubishi Heavy Industries SRK100VNXPZSX Technical Manual page 137

Table of Contents

Advertisement

Error code
Indoor display
Remote control:
E38
Outdoor unit
Outdoor unit
inverter PCB
1. Applicable model
All models
2. Error detection method
Detection of anomalously
low temperature (resistance)
on outdoor air temperature
thermistor
3. Condition of error displayed
• When the temperature thermistor
detects -45°C or lower for 5
seconds continuously within 2
minutes to 2 minutes 20 seconds
after the compressor ON, the
compressor stops. After 3-minutes
delay, the compressor starts again
automatically, but if this anomalous
temperature is detected 3 times
within 40 minutes.
• When -45°C or lower is detected for
5 seconds continuously within 20
second after compressor ON.
4. Presumable cause
• Defective outdoor unit control
PCB
• Broken thermistor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note:
RUN light
Keeps flashing
Green LED
Keeps flashing
control PCB
Yellow LED
Keeps flashing
5. Troubleshooting
the outdoor air
temperature thermistor connector
connected properly?
characteristics of the
outdoor air temperature
thermistor OK?
Temperature-resistance characteristics
(Broken wire)
35
30
25
20
15
10
5
0
(Short circuit)
0
10
TIMER light
Content
1-time flash
Outdoor air temperature
Red LED
1-time flash
Diagnosis
Is
YES
For the characteristics of outdoor air
temperature thermistor, see the following graph.
Is the
YES
20
30
40
50
Temperature (°C)
136
-
-
'17 • PAC-T-257
thermistor anomaly
Countermeasure
Correct connector.
NO
Defective outdoor air
temperature thermistor ➞
NO
Replace.
Defective outdoor unit
control PCB ➞ Replace.
(Defective outdoor air
temperature thermistor
input circuit)