Mitsubishi Heavy Industries SRK100VNXPZSX Technical Manual page 43

Table of Contents

Advertisement

 
5 . Main/Sub setting when more than one remote control are used
Up to two units of R/C can be used
at the maximum for 1 indoor unit or 1
group.
One is main R/C and the other is sub
R/C.
Operating range is different depending
on the main or sub R/C.
Indoor unit
室内ユニット
R/C cable
X Y
リモコン線 (無極性)
(No polarity)
X Y
X Y
リモコン
R/C
リモコン
R/C
"Main"
"Sub"
「親」
「子」
Set the "Main" and "Sub" as
described at Section 8.
Advice: Connection to personal computer
It can be set from a personal computer via the USB port (mini-B).
Connect after removing the cover for USB port of upper case.
Replace the cover after use.
Special software is necessary for the connection.
For details, view the web site or refer to the engineering data.
Advice: Initializing of password
Administrator password (for daily setting items) and
service password (for installation, test run and maintenance) are used.
○ T he administrator password at factory default is "0000". This setting can be changed (Refer to
User's Manual).
I f the administrator password is forgotten, it can be initialized by holding down the [F1] and [F2]
switches together for five seconds on the administrator password input screen.
○Service password is "9999", which cannot be changed.
When the administrator password is input, the service password is also accepted.
R/C operations
Run/Stop, Change set temp,
Change flap direction, Auto swing, Change fan
speed operations
High power operation, Energy-saving operation
Silent mode control
Useful
Individual flap control
functions
Anti draft setting
Timer
Favorite setting
Weekly timer
Home leave mode
External ventilation
Select the language
Energy-saving setting
Filter
Filter sign reset
User setting Initial settings
Administrator
Permission/
settings
Prohibition setting
Outdoor unit silent
mode timer
Setting temp. range
Temp. increment
setting
Set temp. display
R/C display setting
Change administrator
password
F1/F2 function setting ○
42
-
R/C operations
Main Sub
Service
Installation
setting
settings
×
×
×
×
R/C function
settings
×
×
×
×
×
×
IU settings
Service &
Maintenance
-
'17 • PAC-T-257
○: operable ×: not operable
Main Sub
Installation date
Company information
Test run
Static pressure adjustment
Change auto-address
Address setting of main IU
IU back-up function
Infrared sensor (motion sensor)
setting
Main/Sub of R/C
Return air temp.
R/C sensor
R/C sensor adjustment
Operation mode
ºC / ºF
Fan speed
External input
Upper/lower flap control
Left/right flap control
Ventilation setting
Auto-restart
Auto temp. setting
Auto fan speed
IU address
Next service date
Operation data
Error
Error history
display
Display/erase
anomaly data
Reset periodical check
Saving IU settings
Special
Erase IU address
settings
CPU reset
Restore of default setting
Touch panel calibration
Indoor unit capacity display
USB端子
USB port
カバー
Cover
Input password
Input the administrator password.
Delete
Set
Back
Input 4 digit number & tap [Set]
[F1] [F2] switch
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×