Explanation Of The Parameters - Siemens SIMATIC ET 200eco PN M12-L Equipment Manual

Hide thumbs Also See for SIMATIC ET 200eco PN M12-L:
Table of Contents

Advertisement

Modbus TCP
6.1 Functions/parameters/address space
6.1.3

Explanation of the parameters

Diagnostics: Low voltage 1L+
Enabling of the diagnostics for insufficient supply voltage 1L+.
Diagnostics: Short-circuit
Enabling of diagnostics for short-circuit to ground at transducer supply
Diagnostics: Wire break detection and alarm
Activates wire break detection and enabling of diagnostics for the digital input in case of an
interruption of the cable between the encoder and I/O device.
NOTE
Effect on the value status
When the parameter is deactivated, wire break detection is switched off. A wire break does
not have an effect on the value status.
Input delay
This parameter can be used to suppress signal interference. Changes to the signal are only
detected if they are present consistently for longer than the set input delay time.
For input channels with longer input delays, the read-in time is moved accordingly. This
means individual channels can be assigned input delays, if necessary, without having a
negative impact on the possible update time.
Hardware interrupt on rising edge
Specifies whether a hardware interrupt is generated via the data status on a rising edge on
the channel. The hardware interrupt information can be read and confirmed via the event
interface.
A hardware interrupt is only generated for the channel when there is a fault-free signal (value
status/QI = 1). This means no diagnostics is pending for the channel. See also: Address space
(Page 47)
Hardware interrupt on falling edge
Specifies whether a hardware interrupt is generated via the data status on a falling edge on
the channel. The hardware interrupt information can be read and confirmed via the event
interface.
A hardware interrupt is only generated for the channel when there is a fault-free signal (value
status/QI = 1). This means no diagnostics is pending for the channel. See also: Address space
(Page 47)
46
I/O device digital inputs DI 16x24VDC M12-L 8xM12 (6ES7141-6BH00-0BB0)
Equipment Manual, 03/2023, A5E46570510-AD

Advertisement

Table of Contents
loading

Table of Contents