Parameter
The following table shows the parameters of the instruction.
Parameter
Decla-
ration
Req
Input
ActiveRead
Input
Busy
Output
Done
Output
Error
Output
Status
Output
UserData
InOut
Content
TMFAST
InOut
ControlREC
Status parameter
Error codes or status information are output as word at the Status output.
Code
Meaning
(W#16#...)
0000
No error.
7000
No job in progress.
7001
Initialization in progress.
7002
Reading data record 101.
7003
Writing data record 101.
8002
An error has occurred when reading data record 101.
8003
An error has occurred when writing data record 101.
Technology module TM FAST (6ES7554-1AA00-0AB0)
Equipment Manual, 04/2023, A5E52301130-AA
Data type
Default
Bool
False
Bool
False
Bool
False
Bool
False
Bool
False
Word
16#0
DWord array
16#0
[0...m]
LTMFAST_
ControlREC
5.1 Programming with STEP 7 (TIA Portal)
Description
Starts the job at a positive edge.
Writing or reading data record 101:
0: The content of UserDataContent is written to data record 101
1: Data record 101 is read from TM FAST and written to UserDataCon-
tent
Busy = True: The job has not yet been completed.
Done = True is displayed for one cycle or until Req is reset: The job
was completed without errors.
Error = True is displayed for one cycle or until Req is reset: An error
has occurred. In this case, Busy and Done are set to False. For de-
tailed information, see Status parameter.
Status of the instruction, displayed for one cycle or until Req is reset:
see "Status parameter" description
Content of data record 101
Assignment of the instance data block of the LTMFAST_ControlREC
instruction that contains the hardware identifier of the TM FAST
used.
Remedy
If the initialization takes unexpectedly long
time, check if the Error output of
LTMFAST_ControlREC (Page 31) shows an error.
Read the description of the WRREC/RDREC in the
information system of STEP 7 (TIA Portal).
Examples for error codes in the static tag Addi-
tionalErrorID and there remedies:
16#DE80E1A0: Activate the TM FAST appli-
cation.
16#C080B200: Make sure that the CPU can
access the TM FAST.